Example 2
Configuration:
Flow direction = Reverse Only
mA output: LRV = 0 g/s; URV = 100 g/s
(See the second graph in Figure 4-1.)
As a result:
Under conditions of forward flow or zero flow, the mA output of the 
transmitter is 12 mA.
Under conditions of reverse flow, up to a flow rate of 100 g/s, the 
mA output of the transmitter varies between 12 mA and 20 mA in 
proportion to the absolute value of the flow rate.
Under conditions of reverse flow, if the absolute value of the flow 
rate equals or exceeds 100 g/s, the mA output of the transmitter 
will be proportional to the absolute value of the flow rate up to 20.5 
mA, and will be level at 20.5 mA at higher absolute values.
Example 3
Configuration:
Flow direction = Forward Only
mA output: LRV = –100 g/s; URV = 100 g/s
(See the first graph in Figure 4-2.)
As a result:
Under conditions of zero flow, the mA output is 12 mA (before 
respanning).
Under conditions of forward flow, up to a flow rate of 100 g/s, the 
mA output of the transmitter varies between 12 mA and 20 mA in 
proportion to (the absolute value of) the flow rate.
Under conditions of forward flow, if (the absolute value of) the flow 
rate equals or exceeds 100 g/s, the mA output of the transmitter is 
proportional to the flow rate up to 20.5 mA, and will be level at 
20.5 mA at higher flow rates.
Under conditions of reverse flow, up to a flow rate of 100 g/s, the 
mA output of the transmitter varies between 12 mA and 16 mA in 
inverse proportion to the absolute value of the flow rate.
Under conditions of reverse flow, if the absolute value of the flow 
rate equals or exceeds 100 g/s, the mA output of the transmitter is 
inversely proportional to the flow rate down to 11.9 mA (3.8 mA if 
level-shifted), and will be level at 11.9 mA (3.8 mA) at higher 
absolute values.