Honeywell UDC 3300 사용자 설명서

다운로드
페이지 294
104
UDC 3300 Process Controller Product Manual
4/00
Table 4-5
Algorithm Group Definitions, Continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
8SEG CH1
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
8 SEGMENT CHARACTERIZER #1—An eight segment
characterizer can be applied to either Input 1, Input 2,
Output 1, or Output 2.
DISABLE—Disables characterizer.
INPUT 1—Characterizer is applied to Input 1.
INPUT 2—Characterizer is applied to Input 2.
LOOP 1 OUTPUT—Characterizer is applied to Loop 1
Output. (NOTE 1)
LOOP 2 OUTPUT—Characterizer is applied to Loop 2
Output.
There are eight (Xn) Input values and eight (Yn) Output
values to be selected. The following rules apply:
• When Input 2 is used, Input 2 Ratio and Bias are
applied to the Xn Values.
• When one of the Loop outputs are selected, the Xn
Input values are the Output from the control algorithm,
and the Yn Output is the final control element action.
This application is useful for non-linear control elements
or Process Variable.
A simple example is shown in Figure 4-2.
 ATTENTION  The X values below should be entered as increasing values (from 0% to 100%) from N = 0 to 8.
X0 VALUE
0.00 to 99.99 %
X0 INPUT VALUE (X AXIS)
X1 VALUE
0.00 to 99.99 %
X1 INPUT VALUE (X AXIS)
X2 VALUE
0.00 to 99.99 %
X2 INPUT VALUE (X AXIS)
X3 VALUE
0.00 to 99.99 %
X3 INPUT VALUE (X AXIS)
X4 VALUE
0.00 to 99.99 %
X4 INPUT VALUE (X AXIS)
X5 VALUE
0.00 to 99.99 %
X5 INPUT VALUE (X AXIS)
X6 VALUE
0.00 to 99.99 %
X6 INPUT VALUE (X AXIS)
X7 VALUE
0.00 to 99.99 %
X7 INPUT VALUE (X AXIS)
X8 VALUE
0.00 to 99.99 %
X8 INPUT VALUE (X AXIS)
Y0 VALUE
0.00 to 99.99 %
Y0 INPUT VALUE (Y AXIS)
Y1 VALUE
0.00 to 99.99 %
Y1 INPUT VALUE (Y AXIS)
Y2 VALUE
0.00 to 99.99 %
Y2 INPUT VALUE (Y AXIS)
Y3 VALUE
0.00 to 99.99 %
Y3 INPUT VALUE (Y AXIS)
Y4 VALUE
0.00 to 99.99 %
Y4 INPUT VALUE (Y AXIS)
Y5 VALUE
0.00 to 99.99 %
Y5 INPUT VALUE (Y AXIS)
Y6 VALUE
0.00 to 99.99 %
Y6 INPUT VALUE (Y AXIS)
Y7 VALUE
0.00 to 99.99 %
Y7 INPUT VALUE (Y AXIS)
Y8 VALUE
0.00 to 99.99 %
Y8 INPUT VALUE (Y AXIS)