UDC 3300 Process Controller Product Manual
117
4.10   Input 3 Parameters Set Up Group
Introduction
These are the parameters required for Input 3: actuation, transmitter
characterization, high and low range values in engineering units, ratio,
bias, and filter.
 ATTENTION 
 Input 3 prompts appear on expanded models only. Prompts
for Input 3 only appear if Input 2 PWA is installed and the actuation for
Input 2 is configured for one of the following types: 0-5 Vdc, 1-5 Vdc,
0-20 mA, or 4-20 mA.
Input 3 group prompts
Table 4-9 lists all the function prompts in the Input 3 Set Up group and
their definitions.
Table 4-9
Input 3 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN3 TYPE
 ATTENTION  
Changing the input type
will result in the loss of
Field Calibration values
and  will restore Factory
Calibration values.
DISABL
0-20mA
4-20mA
0-5 V
1-5 V
INPUT 3 ACTUATION TYPE – This selection determines
what actuation you are going to use for Input 3.
DISABL—Disables Input 3
0-20mA—0 to 20 milliamperes
4-20mA—4 to 20 milliamperes
0-5 V—0 to 5 volts
1-5 V—1 to 5 volts
XMITTER2
IN3 HI
IN3 LO
RATIO 3
BIAS IN3
FILTER 3
Input 3 ranges and
selections are same as for
Input 1 except Burnout and
Emissivity are not available.
Refer to Input 1 parameters for definitions.