UDC 3300 Controller Product Manual
161
Changing local setpoint
1, 2, or 3
Use the procedure in Table 5-11 to change any of the local setpoint
values.
After changing a local setpoint value, if no other key is pressed, a
minimum of 30 seconds time will elapse before the new value is stored in
nonvolatile memory. If power is removed before this time, the new
setpoint value is lost and the previous setpoint value is used at power up.
If after changing the LSP value another key is pressed, then the value is
stored immediately.
Table 5-11
Procedure for Changing the Local Setpoints
Step
Operation
Press
Action
1
Select the
setpoint
SETPOINT 
SELECT
until you see
Lower Display
Upper Display
The PV value
SP, 2SP, or 3SP and 
the local setpoint value 
or RSP and the remote 
setpoint value
2
Select a different
setpoint or the
remote setpoint
SETPOINT 
SELECT
and hold
in
to cycle through the setpoint type menu as
long as the key is pressed. When the key is
released, the setpoint selection currently
displayed will be the new setpoint selection.
3
Change the
value
 or
to change the local setpoint to the value at
which you want the process maintained.
SP, 2SP, or 3SP indicator will light to match
the lower display.
ATTENTION
 The remote setpoint
cannot be changed at the keyboard.