UDC 3300 Controller Product Manual
4/00
Internal cascade
Figure 5-3 is a block diagram of internal Cascade for a 2-loop controller.
Figure 5-3
Functional Overview Block Diagram of Internal Cascade of a 2-loop Controller
PID 
CONTROL 
ALGORITHM 
Loop 2
OUTPUT
To Final 
Control 
Element
PV SOURCE 
See 
Loop 2
 
Block Diagram
PRIMARY LOOP
PV SOURCE 
See 
Loop 1
 
Block Diagram
SECONDARY LOOP
PID 
CONTROL 
ALGORITHM 
Loop 1
SETPOINT 
SOURCE 
Loop #1
INTERNAL 
OUTPUT 
SIGNAL 
SETPOINT 
SOURCE 
See 
Loop #2
 
Block Diagram
INTERNAL CASCADE RULES
 
•  Loop #2 must be the primary loop. 
•  Loop #1 must be the secondary (internal or slave) loop 
because all output forms exist on Loop 1. 
•  Loop #1 Remote Setpoint is fixed as loop #2 output.
24182
Remote Setpoint
Local Setpoint
SP
2SP
3SP
Override rules
The UDC 3300 allows you to select high or low output override. Refer to
Section 3 - Configuration to select High or Low.
The following rules apply for high/low override:
• Only one physical output is required when override is enabled. It is the
output from Loop 1 because Loop 2’s internal output is routed through
the selector.
• Loop 2 output can also be available at all times if desired.
• In Manual mode, the Output may be overridden.
• Does not apply for Three Position Step Control.
• OTI on bottom display shows value of the internal Loop 1 output
before any override.
ATTENTION
 The output of the unselected loop tracks the selected loop
to within 5 % when in Auto mode to eliminate windup. This tracking is
done in the direction opposite to the Override Select configuration; i.e., for
High Select, the unselected output tracks within 5 % of lower, and vice
versa.