UDC 3300 Controller Product Manual
179
Select tuning
parameters for each
group
The procedure in Table 5-27 shows you how select the Tuning
Parameters.
Table 5-27
Procedure for Selecting Tuning Parameters
Step
Operation
Press
Action
1
Select Tuning
Set Up Group
SET UP
until you see:
TUNING
Lower Display
SET UP
Upper Display
TUNING 2
Lower Display
SET UP
Upper Display
for Loop 1
for Loop 2
or
PID sets 1 and 2 (TUNING) are for Loop 1
and single loop applications.
PID sets 3 and 4 (TUNING 2) are for Loop 2
in two-loop and cascade control applications.
2
Select Tuning
constants
FUNCTION 
LOOP 1/2
to successively display the following
constants:
Lower Display
Upper Display
TUNING CONSTANTS for 
   Primary Loop 
 
PROP BAND or GAIN 
RATE (MIN) 
RESET (MIN OR RPM) 
CYCLE 
PROP BAND2 or GAIN2 
RATE2 (MIN) 
RESET2 (MIN OR RPM) 
CYCLE2 
The Tuning Constant Value
TUNING CONSTANTS for 
  LOOP 2 
 
PROP BAND3 or GAIN3 
RATE3 (MIN) 
RESET3 (MIN OR RPM) 
CYCLE3 
PROP BAND4 or GAIN4 
RATE4 (MIN) 
RESET4 (MIN OR RPM) 
CYCLE4 
OR
Refer to Section 3 - Configuration for
detailed information.
You can Autotune both sets on either loop.
Refer to Section 5.21.
Use the  FUNCTION   key to switch
between loops.
 or
To change the values.