Honeywell UDC 3300 사용자 설명서

다운로드
페이지 294
4/00
UDC 3300 Controller Product Manual
209
6.3  Drawing a Ramp/Soak Profile
Ramp/Soak Profile
example
Before you do the actual configuration, we recommend that you draw a
Ramp/Soak profile in the space provided on the “Program Record Sheet
(Figure 6-2) and fill in the associated information. An example of a
Ramp/Soak Profile is shown in Figure 6-1.
Figure 6-1
Ramp/Soak Profile Example
500
400
200
300
°F
Time/ 
Hours
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
SEG 2
SEG 3
SEG 4
SEG 5
SEG 6
SEG 7
SEG 8
SEG 9
SG 10
SG 11
SG 12
SEG 1
22624
Prompt
Function
Segment
Value
Prompt
Function
Segment
Value
STRT SEG
Start Seg.
1
SEG4TIME
Soak Time
4
1 hr.
END SEG
End Seg.
12
SEG5RAMP
Ramp Time
5
1 hr.:30 min.
RAMP UNIT Engr. Unit for
Ramp
TIME
SEG6 SP
Soak SP
6
250
RECYCLES Number of
Recycles
2
SEG6TIME
Soak Time
6
3 hr.:0 min.
SOAK DEV
Deviation
Value
0
SEG7RAMP
Ramp Time
7
2 hr:30 min.
PROG END
Controller
Status
LAST SP
SEG8 SP
Soak SP
8
500
STATE
Controller
State at end
HOLD
SEG8TIME
Soak Time
8
0 hr.:30 min.
KEYRESET Reset SP
Program
DISABL
SEG9RAMP
Ramp Time
9
0
HOT
START
PV Hot Start
Program
Initialization
or power up
in SPP
DISABL
SG10 SP
Soak SP
10
400
SEG1RAMP Ramp Time
1
1 hr.
SG10 TIME
Soak Time
10
0 hr.:30 min.
SEG2 SP
Soak SP
2
300
SG11RAMP
Ramp Time
11
3 hr:30 min.
SEG2TIME
Soak Time
2
1 hr.:30 min.
SG12 SP
Soak SP
12
200
SEG3RAMP Ramp Time
3
1 hr.
SG12TIME
Soak Time
12
0 hr.:30 min.
SEG4 SP
Soak SP
4
400