UDC 3300 Controller Product Manual
215
Function
Press
Result
External Program
Reset
“To Begin”
If Remote Switching (Digital Input option) is
present on your controller, contact closure
resets the SP Program back to the start of
the first segment.
Program cycle number is not affected.
Reopening the contact has no effect and
places the program in HOLD mode.
The setpoint is changed to what the setpoint
was when the program was first started.
RUN 
HOLD
restarts the Setpoint Program
Keyboard Reset
LOWER 
DISPLAY
until you see
Upper Display
Lower Display
ToBEGIN
Press [
] key to reset program to beginning
at Hold state.
Viewing the present
ramp or soak
segment number
and time
LOWER 
DISPLAY
until you see
Upper Display
R” and the PV value
Lower Display
For Ramp segments:
# RA XX.XX
Segment Number (odd only)
Indicates Ramp segment
Ramp Time - Hours.Minutes or 
Ramp Rate - EU/MIN or EU/HR
For Soak segments:
# SK XX.XX
Segment Number (even only)
Indicates Soak segment
Time remaining in segment in 
Hrs.Minutes including current 
partially completed minute