Honeywell UDC 3300 사용자 설명서

다운로드
페이지 294
4/00
UDC 3300 Process Controller Product Manual
223
7.4  Input #1, #2, or #3 Set Up Wiring
Thermocouple inputs
using an ice bath
Referring to Figure 7-2, wire the controller according to the procedure
given in Table 7-3.
Table 7-3
Set Up Wiring Procedure for Thermocouple Inputs Using an
Ice Bath
Step
Action
1
Connect the copper leads to the calibrator.
2
Connect a length of thermocouple extension wire to the end of each copper
lead and insert the junction points into the ice bath.
3
Connect the thermocouple extension wires to the terminals for Input #1 or
Input #2. See Figure 7-2.
4
Connect a cold junction resistor to terminals 25 and 27 for Input #1 or
terminals 22 and 24 for Input #2. See Figure 7-2.
Figure 7-2
Wiring Connections for Thermocouple Inputs
Using an Ice Bath
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
L1
L2/N
22
23
24
25
26
27
+
Ice Bath
Millivolt  
Source
T/C Extension Wire
Copper Leads
+
24174
C/J Resistor
+
Input 2
Input 1