UDC 3300 Controller Product Manual
4/00
Step
Description
Press
Action
 or 
to select automatic or manual calibration.
Lower Display
Upper Display
POS PROP
DO AUTO 
or 
DO MAN
If you select…
Then…
DO AUTO
go to Step 4
DO MAN
go to Step 6
ATTENTION
 When calibration is terminated, this
selection reverts to DISABL.
4
DO AUTO
Set 0 % value
FUNCTION 
LOOP 1/2
The decrement relay is turned on to move the motor to
0 % position.
Lower Display
Upper Display
ZERO VAL
counts of feedback 
slidewire (0 to 3000)
When the motor stops, the display should stop counting,
then go to the next step.
5
DO AUTO
Set 100 % value
FUNCTION 
LOOP 1/2
The increment relay is turned on to move the motor to
100 % position.
Lower Display
Upper Display
SPAN VAL
counts of feedback 
slidewire (0 to 3000)
When the motor stops, the display should stop counting,
then, go to Step 8.
6
DO  MAN
Set 0 % value
FUNCTION 
LOOP 1/2
You will see:
Lower Display
Upper Display
ZERO VAL
The existing zero 
calibration value 
in counts.
 or 
until the desired zero value is reached in the upper
display.
Lower Display
Upper Display
ZERO VAL
The desired zero 
value
7
DO  MAN
Set 100 % value
FUNCTION 
LOOP 1/2
The controller will store the 0 % value and you will see:
Lower Display
Upper Display
SPAN VAL
The existing span 
calibration value 
in counts