UDC 3300 Controller Product Manual
23
Time proportional
output, continued
Figure 2-9 shows the Output and Alarm wiring connections for models
with Solid State Relay Output (Model DC330X-AA-XX).
For Control and Alarm Relay Contact information, see Tables 2-7 and 2-8.
Figure 2-9
Solid State Relay Output—Model DC330X-AA-XX
Alarm 
Relay#2
Alarm 
Relay#1
L1
L2/N
22
23
24
25
26
27
Output 
Relay#1
To terminal 
7 or 9
To terminal 
4 or 6
AC Load 
Supply 
Power
Relay Load
Dummy Resistor
N.O.
1
2
3
4
5
6
7
8
9
Time Proportional
 Duplex 
Time Proportional
 Simplex
Alarm 
Relay#1
L1
L2/N
22
23
24
25
26
27
Output 
Relay#1
To terminal 
7 or 9
Output 
Relay#2
AC Load 
Supply 
Power
Relay Load
Dummy Resistor 
N.O.
N.O.
AC Load 
Supply 
Power
Relay Load
Dummy Resistor 
If the load current is less than the minimum rated value of 20 mA, there may be a residual voltage across both ends of 
the load even if the relay is turned off. Use a dummy resistor as shown to counteract this. The total current through the 
resistor and the load current must exceed 20 mA.
2
3
Alarm #2 not available with Time Proportional Duplex or Three Position Step Control or Position Proportional control.
1
Solid State relays are rated at 0.5 amps. Customer should size fuses accordingly. Use Fast Blo fuses only.
1
1
3
3
2
3
1
1
2
3
4
5
6
7
8
9
N.C.
N.C.
N.O.
N.O.
N.C.
N.O.
AC Load 
Supply 
Power
Alarm Relay #2 Load
AC Load 
Supply 
Power
Alarm Relay #1 Load
AC Load 
Supply 
Power
Alarm Relay #1 Load
24164
Electromechanical relays are rated at 5 Amps @120 Vac or 30 Vdc and 2.5 Amps at 240 Vac. 
Customer should size fuses accordingly. Use Fast Blo fuses only. 
WARNING: Only connect Vac to solid state relays.
4
4
4
4