UDC 3300 Controller Product Manual
4/00
Current output/
universal output
connections
Figure 2-12 shows the Output and Alarm wiring connections for models
with Current Output (Model DC330X-KE-XXX and Model
DC330X-C0-XXX
). See Table 2-5 for wiring restrictions.
For Control and Alarm Relay Contact information, see Tables 2-7 and 2-8.
Figure 2-12
Current Output—Current /Time Duplex, Time/Current Duplex, Position Proportional,
or Three Position Step Control
+
ATTENTION: 
All current outputs are isolated from each other, case ground, and all inputs.
L1
L2/N
22
23
24
25
26
27
10
11
12
Controller Load 
0–1000 Ohms
Current Output 
4–20 mA
N.C.
N.O.
N.O.
N.C.
For Duplex Current Output use Auxiliary Output for Output 2 (cool) (see Figure 2-14).
To terminal 
7 or 9
Output#1 
or 
Alarm#2 
Relay
To terminal 
4 or 6
Load 
Supply 
Power
Output or Alarm 
Relay 2 Load
Load 
Supply 
Power
Output or Alarm 
Relay 3 Load
24167
Output#2 
or 
Alarm#1 
Relay
See Table 2-7 for relay 
terminal connections for 
Output Algorithm selected.
1
2
3
4
5
6
7
8
9
Electromechanical relays are rated at 5 Amps @120 Vac or 2.5 Amps at 240 Vac. 
Customer should size fuses accordingly. Use Fast Blo fuses only. 
Relays are NOT available on DC330X-C0-XXX.
1
1
1
Table 2-5
Universal Output Wiring Functionality and Restrictions for Figure 2-12
Controller with Two Current Outputs and Two Relay Outputs
SINGLE LOOP OR CASCADE CONTROL OUTPUT
Output Type
Current
Auxiliary
Relay #1
Relay #2
Relay #3
Time Simplex
Not used
Not used
N/A
Output 1
Alarm 1
Current
Output 1
Not used
N/A
Alarm 2
Alarm 1
Position (not available on
Cascade Control)
Not used
Not used
N/A
Output 1
Output 2
Time Duplex or TPSC
Not used
Not used
N/A
Output 1
Output 2
Current Duplex 100%
Output 1
Not used
N/A
Alarm 2
Alarm 1
Current Duplex 50%
Output 1
Output 2
N/A
Alarm 2
Alarm 1
Current/Time or
Time/Current
Output 1 or 2
Not used
N/A
Output 1 or 2
Alarm 1