Honeywell UDC 3300 사용자 설명서

다운로드
페이지 294
32
UDC 3300 Controller Product Manual
4/00
Transmitter power for
4-20 mA 2-wire
transmitter—open
collector alarm 2 output
The wiring diagram example shown in Figure 2-19 (Model
DC330X-XT-XXX
) provides 30 Vdc at terminals 5 and 6 with the
capability of driving up to 22 mA, as required by the transmitter which is
wired in series.
If the transmitter terminal voltage must be limited to less than 30 volts,
you can insert a zener diode between the positive transmitter terminal and
terminal 5. For example, an IN4733A zener diode will limit the voltage at
the transmitter to 25 Vdc.
Configure:
A2S1TYPE = NONE
A2S2TYPE = NONE
Figure 2-19
Transmitter Power for 4-20 mA 2-wire Transmitter Using Open Collector Alarm 2
Output—Model DC330X-XT-XXX
24171
1
2
3
4
5
6
7
8
9
L1
L2/N
22
23
24
10
11
12
13
14
15
16
17
25
26
27
+
2-wire 
Transmitter
250 ohm 
resistor
+
+
If necessary, install zener diode here to 
reduce voltage at transmitter.