UDC 3300 Process Controller Product Manual
4/00
3.7
Loop 2 Tuning Parameters Set Up Group (Cascade or
Two Loops
Two Loops
Function prompts
Table 3-4 lists all the function prompts in the Tuning 2 Set Up group. This
group is only displayed if the controller is configured for Cascade or
2-Loop control (prompt PIDLOOPS in Algorithm Data Set Up group).
group is only displayed if the controller is configured for Cascade or
2-Loop control (prompt PIDLOOPS in Algorithm Data Set Up group).
Table 3-4
Tuning Loop 2 Group Function
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PROPBD3
or
GAIN 3
Proportional Band 3
or
Gain 3
or
Gain 3
0.1 to 9999
0.001 to 1000
- -
1.000
Section
4.3
or
GAINVALn
or
Gain Value being used by
Gain Scheduling when
enabled
Gain Value being used by
Gain Scheduling when
enabled
Read Only
- -
RATE3MIN
Rate 3 in Minutes
0.00 to 10.00 minutes
0.00
RSET3MIN
or
RSET3RPM
Reset 3 in minutes/repeat
or
Reset 3 in repeats/minute
or
Reset 3 in repeats/minute
0.02 to 50.00
1.00
- -
MANRSET3
Manual Reset 3
–100 to 100 % Output
0.0
PROPBD4
or
GAIN 4
Proportional Band 4
or
Gain 4
or
Gain 4
0.1 to 9999 %
0.001 to 1000
- -
1.000
RATE4MIN
Rate 4 in Minutes
0.00 to 10.00 minutes
0.00
RSET4MIN
or
RSET4RPM
Reset 4 in minutes/repeat
or
Reset 4 in repeats/minute
or
Reset 4 in repeats/minute
0.02 to 50.00
1.00
- -
CYC3 SEC*
or
CYC3 SX3*
Cycle Time 3 (Heat)
1 to 120
20
CYC4 SEC*
or
CYC4 SX3*
Cycle Time 4 (Cool)
1 to 120
20
PVEUVAL1
PVEUVAL2
PVEUVAL3
PVEUVAL4
PVEUVAL5
PVEUVAL6
PVEUVAL7
PVEUVAL8
PVEUVAL2
PVEUVAL3
PVEUVAL4
PVEUVAL5
PVEUVAL6
PVEUVAL7
PVEUVAL8
PV1 (through PV8) Value for
Gain Scheduling
Gain Scheduling
PV value within the PV limits.
In engineering units
In engineering units
0
GAINVAL1**
GAINVAL2**
GAINVAL3**
GAINVAL4**
GAINVAL5**
GAINVAL6**
GAINVAL7**
GAINVAL8**
GAINVAL2**
GAINVAL3**
GAINVAL4**
GAINVAL5**
GAINVAL6**
GAINVAL7**
GAINVAL8**
Gain 1 (through Gain 8)
Value for Gain Scheduling
Value for Gain Scheduling
0.001 to 1000 floating
Gain or Proportional Band
Gain or Proportional Band
1.000
*Cycle times are in either 1 second or 1/3 second increments, depending upon the RLY TYPE configuration in the
Output Algorithm Set Up group.
** ATTENTION If units of percent proportional band (PB) are selected under the Control Set Up prompt, function
prompt PBorGAIN, then the displayed values are in %PB, but the lower display will still show Gain.
Output Algorithm Set Up group.
** ATTENTION If units of percent proportional band (PB) are selected under the Control Set Up prompt, function
prompt PBorGAIN, then the displayed values are in %PB, but the lower display will still show Gain.