UDC 3300 Process Controller Product Manual
4/00
Function prompts
Table 3-6 lists the function prompts in the Accutune Set Up group.
Table 3-6
Accutune Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
FUZZY
Fuzzy Overshoot
Suppression
DISABL
ENABLE
ENABL2
ENAB12
DISABL
Section
4.5
ACCUTUNE
Accutune—Loop 1
DISABL
TUNE (Demand Tuning)
SP (SP Tuning)
TUN+PV
SP+PV
DISABL
ACCUTUN2
Accutune—Loop 2
DISABL
TUNE (Demand Tuning)
SP (SP Tuning)
TUN+PV
SP+PV
DISABL
SP CHANG*
Setpoint Change Value—
Loop 1
5 to 15 % Input Span
10
KPG*
Process Gain—Loop 1
0.10 to 10.00
1.00
SP CHAN2*
Setpoint Change Value –
Loop 2
5 to 15 % Input Span
10
KPG 2*
Process Gain – Loop 2
0.10 to 10.00
1.00
CRITERIA*
Tuning Criteria—Loop 1
NORMAL
FAST
FAST
CRITERA2*
Tuning Criteria – Loop 2
NORMAL
FAST
FAST
AT ERROR
or
AT ERR 2
(depending on
Loop)
Accutune Error Codes
Read Only
RUNING (Accutune process in 
operation)
NONE
OUTLIM
IDFAIL
ABORT
LOW PV
- -
*Applies to SP and SP+PV only.