UDC 3300 Process Controller Product Manual
4/00
3.12 
Input 1 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 1.
Function prompts
Table 3-9 lists all the function prompts in the Input 1 Set Up group.
Table 3-9
Input 1 Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
IN1 TYPE
Input 1 Actuation Type
DISABL
W TC H
B TC
W TC L
E TC H
100 PT
E TC L
100 LO
J TC H
200 PT
J TC L
500 PT
K TC H
RAD RH
K TC L
RAD RI
NNM H
0-20mA
NNM L
4-20mA
NM90 H
0-10mV
NM90 L
0-50mV
NIC TC
0-5 V
R TC
1-5 V
S TC
0-10 V
T TC H
CARBON
T TC L
OXYGEN
0-10mV
Section
4.8
XMITTER1
Transmitter Characterization
B TC
S TC
E TC H
T TC H
E TC L
T TC L
J TC H
W TC H
J TC L
W TC L
K TC H
100 PT
K TC L
100 LO
NNM H
200 PT
NNM L
500 PT
NM90 H
RAD RH
NM90 L
RAD RI
NIC TC
LINEAR
R TC
SQROOT
ANALYT*
LINEAR
ANALYTIC*
Analytic Selections
XMITTER1 must be set to
ANALYT for this prompt to
appear
NONE
PH
ORP mV
CONDmS
CONDuS
RSTVM^
TDS PPm
TDS PPb
CONCPt
DO PPm
DO PPb
NONE
IN1 HI
Input 1 High Range Value
(Linear Inputs only)
–999. To 9999. Floating
(in engineering units)
1000
IN1 LO
Input 1 Low Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
0
RATIO 1
Input 1 Ratio
–20.00 to 20.00
(floats to 3 decimal places)
1.000