Appendix E. Sensor Data for Calibration.
Resistance Sensors.
Sensor Type:
C7100A1015, (and C7170A1002).
Sensor Use:
Discharge air, Outdoor air.
Table E-1 lists the points for Sensor Resistance versus Temperature. Fig. E-1 shows the graph of these points.
Table E-1. Sensor Resistance Versus Temperature.
°F (°C)
Resistance Ohms
-40 (-40)
2916.08
-30 (-34.5)
2964.68
-20 (-28.9)
3013.28
-10 (-23.3)
3061.88
0 (-17.8)
3110.48
10 (-12.2)
3159.08
20 (-6.7)
3207.68
30 (-1.1)
3256.28
40 (4.4)
3304.88
50 (10)
3353.48
60 (15.6)
3402.08
70 (21.1)
3450.68
80 (26.7)
3499.28
90 (32.2)
3547.88
100 (37.8)
3596.48
110 (43.4)
3645.08
120 (49)
3693.68
3050
3000
2950
2900
3100
3150
3200
3250
3300
3350
3400
3450
3500
3550
3600
3650
3700
3750
50
40
30
20
10
0
-10
-20
-30
-40
60 70
80
90 100 110 120
10
4.4
-1.1
-6.7
-12.2
-17.8
-23.3
-28.9
-34.5
-40
15.6
21.1
26.7
32.2
37.8
43.4
49
OHMS
°
F
°
C
SENSOR RESISTANCE VERSUS TEMPERATURE
M11959
Fig. E-1. Graph of Sensor Resistance versus Temperature.
Sensor Type:
C7031B1033, C7031C1031, C7031D1062, C7031F1018, C7031J1050, C7031K1017.
Sensor Use:
Return Air, Discharge Air Temperature.