Lg Electronics 120S 사용자 설명서

다운로드
페이지 306
Chapter 3  General Specifications  
3-1 
 
 
Chapter 3. General Specifications   
 
3.1 General Specifications 
 
The following table shows the general specifications of the MASTER-K120S series.   
 
No. 
Item 
Specifications 
References 
Operating ambient 
Temperature 
0 ~ 55 
°C 
 
Storage ambient 
Temperature 
−25 ~ +70 °C 
 
Operating ambient 
Humidity 
5 ~ 95%RH, non-condensing 
 
Storage ambient 
Humidity 
5 ~ 95%RH, non-condensing 
 
Occasional vibration 
 
Frequency Acceleration  Amplitude  Sweep 
count 
10 
≤ f < 57Hz 
− 
0.075mm 
57 
≤ f ≤ 150Hz 
9.8m/s
2
 {1G} 
− 
Continuous vibration 
Frequency Acceleration  Amplitude 
10 
≤ f < 57Hz 
− 
0.035mm 
5 Vibrations 
57 
≤ f ≤ 150Hz 
4.9m/s
2
 {0.5G} 
− 
10 times for each 
X, Y, Z axis 
IEC 61131-2 
6 Shocks 
• Maximum shock acceleration: 147 m/s
2
 {15G} 
• Duration time: 11ms 
• Pulse wave: half sine pulse ( 3 shocks per axis, on X, Y, Z axis ) 
IEC 61131-2 
Square wave   
Impulse noise 
± 1,500 V 
LGIS’ Internal 
Standard  
Electronic 
discharge 
Voltage: 4 kV ( Discharge by contact ) 
IEC 61131-2, 
IEC 1000-4-2 
Radiated 
electromagnetic 
field noise 
27 ~ 500 MHz, 10 V/m 
IEC 61131-2, 
IEC 1000-4-3 
Item Power 
supply 
Digital I/O 
(24V and up)
Digital I/O 
(less than24V) 
Analog I/O 
Interface 
7 Noise 
Immunity 
Fast transient & 
burst noise 
Voltage 
2kV 1kV 0.25kV 
IEC 61131-2 
IEC 1000-4-4 
Atmosphere 
Free of corrosive gases and excessive dust 
 
Altitude 
Up to 2,000m   
 
10 
Pollution degree 
2  
 
11 
Cooling method 
Air-cooling  
 
 
 
 
 
 
 
 
1)
 IEC (International Electrotechnical Commission): An international civilian institute who establishes international standards in area of electric
and electronics. 
2) Pollution degree: An indicator, which indicates pollution degree, which determine insulation performance of equipment. 
* Pollution degree 2 : Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by
condensation shall be expected.
REMARK