Programming the VT1422A for Data Acquisition and Control   99
Start Algorithms
Approximately 2000 lines of user-written 'C' code can be downloaded into 
the VT1422A's memory and can be split among up to 32 algorithms. 
VXI Technology refers to these as algorithms because an algorithm is a 
step-by-step procedure for solving some problem or accomplishing some 
end. Though the documentation continues to refer to the 'C' code as 
algorithms, they can be thought of in traditional terms, with each algorithm 
representing a 'C' function with a main() program which calls them.
The user-written 'C' algorithms execute after all analog/digital inputs have 
been stored in the Input Buffer. The 'C' code accesses the measurement data 
like constants with the names of I100-I163 (for on-board channels) and 
I10000-I15731 (for remote channels) representing the 32-bit real 
EU-converted numbers. As seen in Figure 4-1, the algorithms have access to 
both local and global variables and arrays. The I-variables are inherently 
global and accessible by any algorithm. Local variables are only visible to 
the particular algorithm (just like in 'C' functions). Declared global variables 
can be shared by any algorithm. 
Communicating with
Algorithms
The application program can read or write any local or global variable in any 
algorithm by using SCPI syntax that actually identifies the variable by name, 
but a more efficient means of reading data is available through the 
VT1422A's FIFO and Current Value Table (CVT). As seen in Figure 4-1, 
any algorithm can write any expression or constant to the FIFO/CVT. The 
application can then read the FIFO/CVT to characterize what's happening 
inside the VT1422A and to provide an operator view of any input/output 
channel, variable, or constant.
Algorithms Control
Output Values
Output SCP's derive their channel values from O-variables that are written 
by the algorithms. O100-O163 are read/write global variables that are read 
after all algorithms have finished executing. The 32-bit real values are 
converted to the appropriate units as defined by the SCPI configuration 
commands and written to the various output SCP's by channel number.
Figure 4-2. Instrument Operation Cycle Phases
Algorithm 1
Algorithm 2
Algorithm 3
Algorithm 5
Chan
nel
 3
2
Chan
nel
 3
3
Chan
nel
 3
4
Chan
nel
 3
5
Chan
nel
 3
6
Chan
nel
 3
7
Chan
nel
 3
8
Input Channels
Upda
te
 V
a
ria
b
le
 Chan
ges
Check S
c
an S
tat
us and
Updat
e S1
xx V
a
ri
abl
es
Algorithm 4
Output Channels
Chan
nel
 0
Chan
nel
 1
Chan
nel
 2
Chan
nel
 7
Chan
nel
 1
6
PHASE 1 (input)
PHA
S
E
 2
P
HAS
E 1A
(o
pti
ona
l)
PHASE 3 (execute algorithms)
PHASE 4 (output)
Trigger Period
Output Delay Time