500 Example PID Algorithm Listings  
PIDC Algorithm
PIDC is very similar to PIDB with the addition of extended history mode. 
See comments in source code below.
PIDC Source Listing
/********************************************************************************************/
/*  PID_C
*/
/********************************************************************************************/
/*  I/O Channels
*/
/*  Must be defined by the user
*/
/*                  
*/
/* inchan - Input channel name      
*/
/* outchan - Output channel name             
*/
/* alarmchan  - Alarm channel name          
*/
/*                      
*/
/********************************************************************************************/
/*                    
*/
/********************************************************************************************/
/* PID algorithm for VT1422A controller module.  This algorithm is called */
/* once per scan trigger by main().  It performs Proportional,
*/
Integral      
*/
/* and Derivative control.                                                   
*/
/*                                                                           
*/
/*                                                                           
*/
/* The output is derived from the following equations:  
*/
/*                                                                           
*/
/* PID_out = P_out + I_out + D_out + SD_out         
*/
/* P_out = Error * P_factor                            
*/
/* I_out = I_out + (Error * I_factor)      
*/
/* D_out = ((PV_old - PV) * D_factor) 
*/
/* SD_out = (Setpoint - Setpoint_old) * SD_factor 
*/
/* Error = Setpoint - PV           
*/
/*
*/
/* where:                                   
*/
/*   Setpoint is the desired value of the process variable (user supplied)   */
/*   PV is the process variable measured on the input channel
*/
/*   PID_out is the algorithm result sent to the output channel
*/
/*   P_factor, I_factor, D_factor and SD_factor are the PID constants
*/
/*  (user supplied)
*/
/*
*/
/*  Alarms may be generated when either the ProcessVariable or the
*/
/*  error exceeds user supplied limits.
*/
/*  The alarm condition will cause an interrupt to the host computer,
*/
/*  set the (user-specified) alarm channel output to one (1) and set a bit */
/*  in the Status variable to one (1).
*/
/*  The interrupt is edge-sensitive. ( It will be asserted only
*/
/* on the transition into the alarm state.)  The alarm channel digital
*/
/* output will persist for the duration of all alarm conditions.  The
*/
/* Status word bits will also persist for the alarm duration.  No user
*/
/* intervention is required to clear the alarm outputs.
*/
/* */
/* This version provides for limiting (or clipping) of the Integral,
*/
/* Derivative, Setpoint Derivative and output to user specified limits.
*/
/* The Status Variable indicates when terms are being clipped.
*/
/*
*/
/* Manual control is activated when the user sets the Man_state variable */
/* to a non-zero value.  The output will be held at its last value.  The
*/
/* user can change the output by changing the Man_out variable.  User */
/* initiated changes in Man_out will cause the output to slew to the
*/
/* Man_out value at a rate of Man_inc per scan trigger.
*/
/*
*/
/* Manual control causes the Setpoint to continually change to match
*/
/* the Process Variable and the Integral term to be constantly updated
*/
/* to the output value such that a return to automatic control will
*/
/* be bumpless and will use the current Process Variable value as the
*/
/* new setpoint.
*/
/* The Status variable indicates when the Manual control mode is active. */
/*
*/