SITRANS LR 460 (PROFIBUS PA) – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
J;
 P
rof
i;
e
 st
ruct
ur
e
 P
A
Electronics temperature
The Level Transducer Block also monitors the internal temperature of the device 
electronics. If the temperature exceeds permitted limits, it does not change the sensor 
value, but it does change the status.The permitted limits correspond to those of the 
permitted ambient temperature. 
If a temperature limit is exceeded, the status changes. Peak indicators
1
 allow you to 
check the maximum and minimum temperatures that have occurred.
Analog Input Function Blocks 1 and 2
There are two identical Analog Input Function Blocks which operate independently. The 
figure below shows how measured values are processed within the Analog Input 
Function Block (AIFB1 or AIFB2) to produce the device output, which is communicated via 
cyclic transfer to PROFIBUS PA, and displayed on the LCD.
Analog Input Function Block function groups (simulation, mode and status)
2
How the AIFBs work
The Analog Input Function Blocks allow you to control modifications to the output value 
(PROFIBUS cyclic data). 
1.
Open View menu, scroll down to Peak Values, and click on Temperature tab in the 
Peak Values window.
2.
The output from the Level Transducer Block can be called the Primary Value (or 
Secondary Value). When it becomes the input to the AIFB, it is called the Process 
Variable.
enable
on
FB 
algorithm
Status
OUT
AUTO
MODE and 
STATUS 
handling
Process Variable
 
from TB 
(Function Block 
input)
Value Status
Alarm 
Limit 
Check
Out of 
Service
OUT
MAN
Value 
simulate 
value and 
status
Value  Status
Operator
Operator
off
Simulate 
Parameter
Fail-safe
no 
output