SITRANS LR 460 – INSTRUCTION MANUAL 
7ML19985JM01
m
mmmm
Wi
rng
4.
Thermal Data for 7ML5426 Series 
5.
The equipment has not been assessed as a safety related device (as referred to by 
Directive 94/9/EC Annex II, clause 1.5).
6.
Installation and inspection of this equipment shall be carried out by suitably trained 
personnel in accordance with the applicable code of practice (EN 61241-14 and EN 
61241 –17 in Europe).
7.
Repair of this equipment shall be carried out by suitably trained personnel in 
accordance with the applicable code of practice.
8.
Components to be incorporated into or used as replacements in the equipment shall 
be fitted by suitably trained personnel in accordance with the manufacturer’s 
documentation.
9.
It is the user’s responsibility to ensure that a manual override is possible in order to 
shut down the equipment, and that protective systems are incorporated within 
automatic processes which deviate from the intended operating conditions, 
provided that this does not compromise safety.
10. Equipment Marking: The equipment marking contains at least the information on the 
product label. See 
11. If the equipment is likely to come into contact with aggressive substances, it is the 
user’s responsibility to take suitable precautions to prevent it from being adversely 
affected, and to ensure that the type of protection is not compromised.
• Aggressive substances include, for example, acidic liquids or gases that may 
attack metals, or solvents that may affect polymeric materials. 
• Suitable precautions include, for example, regular checks as part of routine 
inspections, or establishing from the material’s data sheet that it is resistant to 
specific chemicals.
SPECIAL CONDITIONS FOR SAFE USE
The ‘X’ suffix to the certificate number relates to the following special condition(s) for 
safe use.
• Cable or conduit entries must meet the requirements of European Directive 
94/9/EC for Group II, Category 1D, 1/2D, or 2D, as appropriate, and must 
maintain the overall IP rating of the enclosure.
• For applications that require the purge feature, the user shall implement a 
means to ensure that combustible dust from the hazardous area cannot enter 
the purge supply in such a way as to compromise the area classification. 
Device 
category
Permitted ambient 
temperature at horn antenna
Permitted ambient 
temperature at electronic 
enclosure
1D, 1/2D, 2D
–40 °C (–40 °F) 
≤ T
amb
 
≤+200°C 
(+392 °F)
–40 °C (–40 °F) 
≤ T
amb
 
≤ +65°C 
(+149 °F)