3. Input 
   Static Revision Number
The revision level of the static data associated with the Level Transducer Block, 
updated whenever a standard profile configuration parameter is changed.
   Class
Indicates the Level Transducer Block as per PROFIBUS PA Profile specifications.
3.2. Standard Setup
3.2.1. Antenna
Identifies antenna configuration.
3.2.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target 
range.
1
Use a setting just faster than the maximum filling or emptying rate (whichever is 
greater). Slower settings provide higher accuracy and a smoother output signal: 
faster settings allow for more level fluctuation.
Options
3" HORN
4" HORN
Related 
parameters
Response
Rate
LOE Timer
(minutes)
Fill Rate
Empty Rate
Values
*
SLOW
100
 0.1 m/minute
 0.1 m/minute
MED
10
1 m/minute
1 m/minute
FAST
1
10 m/minute
10 m/minute
Note: 
If you change Response Rate it resets the following parameters: LOE 
Timer, Fill Rate, and Empty Rate. 
1.
For instructions on usage see 
. For technical details 
.