SITRANS LR 460 – INSTRUCTION MANUAL 
7ML19985JM01
m
mmmm
B:
 T
ro
u
bl
es
h
o
o
tin
g
Reads empty 
when vessel not 
empty.
Reads vessel bottom 
through low dK material.
Increase TVT manually at vessel bottom 
region.
Set Far Range to a lower value.
Lower TVT hover level.
Reading 
fluctuates.
Due to solids’ sloped 
surfaces some fluctuation 
is normal.
Reduce response rate.
Decrease fill/empty parameter values.
Increase filter time constant in AIFB.
Echo has double 
peak/is split
Increase Echo Reform.
Reading is too 
slow and lags 
behind actual 
level change.
Increase response rate.
Turn off Window tracking.
Change fill/empty rate parameter 
values.
Increase filter time constant in AIFB.
Device cannot 
be programmed 
via the 
handheld 
programmer
Make sure local operation is enabled. 
See 
Also make sure that Write Locking is 
Off. See 
You are unable 
to modify a 
parameter via 
remote 
communications
Make sure remote operation is 
enabled. See 
on page 46. Also make sure 
that Write Locking is Off. See 
Troubleshooting LR 460 (cont’d)
Symptom
Possible cause
Remedy