Grounding Examples: SITRANS LC 500
Grounding is important for two reasons: 
1.
To prevent interference to the signal: system grounding
2.
For safety purposes: safety grounding
Several common applications are illustrated. They are separated into two groups: the first 
group illustrates System Grounding and the second illustrates Safety Grounding.
System Grounding (referencing)
For the measuring system to function correctly, the reference electrode must be properly 
grounded. Make sure that there is a reliable connection from the instrument housing to 
the reference electrode (usually a metal tank). Some common applications involving 
system grounding include: 
• metal tanks
• metal tanks, cathodically protected
• non-conductive tanks
Metal Tanks
If the metal tank is reliably 
grounded, connect the ground lug 
on the SITRANS LC 500 to the 
earth ground on the tank as 
shown. 
(See page 26 for connection 
diagram.)
ground lug