Siemens LC 500 사용자 설명서

다운로드
페이지 122
7ML19985GE01
SITRANS LC 500 – INSTRUCTION MANUAL
Page 77
mm
mmm
A
ppendi
x C
HART Response Code Information
Additional response code information, Second Byte.
Bit #7: Field Device Malfunction
When the transmitter detects a malfunction, the Analog Output will be set in a fault state.
Bit #6: Configuration Changed
When any of the settings in EEROM is changed either by a write command or by manual 
ZERO or SPAN adjust, this bit is set. Use command 38 to reset.
Bit #5: Cold Start
This bit is issued once after an initialisation cycle is complete; this can occur after a 
power loss or as a result of a (watchdog) reset.
Bit #4: Extended Status Available
When any of the extended status bits is set this flag is raised. Use command 48 to get 
detailed status information.
Bit #3: Output Current Fixed
This bit is set as long as the Primary Variable Analog Output is set to a fixed value.
Bit #2: Primary Variable Analog Output Saturated
Flag is set when the Primary Analog Output saturates below 3.8 mA and above 20.5 mA.
Bit #0: Primary Variable Out of Limits
This flag is set whenever the Transmitter Variable #0 (in pF), the Primary Variable exceeds 
the Sensor Limits returned with Command 14, Read Primary Variable Sensor Limits.