Application: level indicator and solid-state switch output
The loop current provides:
a reading proportional to level, within the 0 - 100% range, at menu 00 or 10 on the 
device, or at a remote indicator
an out-of-range signal ooL alternating with PV if the level is above URV or below 
LRV 
The solid-state switch is activated at Upper Threshold Setting and deactivated at Lower 
Threshold Setting. In the diagram below, it is used to activate a pump via an auxiliary 
power circuit.
The activation and deactivation can be modified by Upper and/or Lower Threshold 
delays (menus 13 and 14).
The reading can be stabilized if necessary by applying Damping (menu 0A): the 
update value for Damping is controlled by menu 09.
Example: 
The level is to be held between 90% and 8%.
Device settings: 
(The device is first restored to factory settings before being commissioned)
TV0 selected: Transmitter Variable 0 is PV
Menu 01 reads Pv = 0
Lower Range Value (0% of range) is set to 14.3
Menu 0E reads  14.30
Upper Range Value (100% of range) is set to 75.8. 
Menu 0F reads  75.80
Current loop is in analog mode, with both buttons pressed
Menu 07 reads  C:An
Solid-state switch enabled, contact closed selected
Menu 17 reads  S:cc
1
Activation hysteresis is set to 90.
Menu 15 reads 90.0
Deactivation hysteresis is set to 8.
Menu 16 reads 08.0.
When the level reaches 90%, the solid-state output is closed and the pump is started via 
the auxiliary circuit. When the level drops to 8% the solid-state output is opened, the 
auxiliary circuit is deactivated, and the pump stops. 
1.
S:cc appears while the button is pressed. See menu 17 on page 70 for more details.
P
Indicator: primary variable viewed at menus 00 or 01; 
units or% selected in menu 01 
0-100%
auxiliary 
power
pump 
power
solid-
state 
output
current loop connection
(menu 0F) URV = 100%
Upper Threshold Setting = 90%
menu 15 (activation hysteresis)
menu 16 (deactivation hysteresis)
Lower Threshold Setting = 8%
(menu 0E) LRV = 0%
(menu 0C) USL
(menu 0B) LSL
solid-state 
switch 
output: 
selected at 
menu 17 
and 
controlled 
by menus 
13 to 18.
75.8 pF
14.3 pF
Active Shield section