Customer environment
November 2004
Avaya Modular Messaging Concepts and 
Planning Guide
B-3
Site requirements for Avaya servers
This section describes the physical requirements for the installation site, 
including environmental, weight, space, and power considerations for an 
Avaya Messaging Application Server (Avaya MAS) and the Avaya 
Message Storage Server (MSS—S, standard availability and MSS—H, 
high-availability).
Environmental requirements
Table B-1 lists the environmental conditions that must be maintained in 
the area where the Avaya servers are installed and maintained.
Table  B-1. Environmental requirements
Weight and space considerations
Table B-2 lists the weight, height, width, and depth of each MAS and the 
MSS.
Table  B-2. Avaya MAS weight and space considerations
For safety considerations, at least two technicians should be on site and 
available to mount the units.
Operating state
Temperature
Maximum heat output
Humidity 
(noncondensing)
Operating
+10 to +35ºC
(+50 to +95ºF)
MAS: 730 BTU/hour
MSS-S: 352 BTU/hour
MSS-H: 682 BTU/hour
20% to 80% RH
Non-operating 
(in storage or being 
shipped)
-20 to +50ºC
(-4 to+122ºF)
N/A
20% to 90% RH
Server
Weight (full)
Height
Width
Depth
Avaya MAS
40 lb.
(18.1 kg)
(without port boards)
6.8 in.
(17 cm)
16.9 in.
(43 cm)
18.9 in.
(48 cm)
Avaya MSS-S
41 lb.
(18.6 kg)
6.8 in.
(17 cm)
16.9 in.
(43 cm)
18.9 in.
(48 cm)
Avaya MSS-H
52 lb.
(23.6 kg)
6.8 in.
(17 cm)
16.9 in.
(43 cm)
18.9 in.
(48 cm)