ANN-BUS Devices
Installation
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
31
After calculating the total worst case current draw, Table 2.1  specifies the maximum distance 
the modules can be located from the FACP on a single wire run.  The table ensures 6.0 volts of 
line drop maximum.  In general, the wire length is limited by resistance, but for heavier wire 
gauges, capacitance is the limiting factor. 
These cases are marked in the chart with an asterisk (*).  Maximum length can never be more 
than 6,000 feet (1,800 m), regardless of gauge used.  The formula used to generate this chart is 
shown in the note below.
Note:   The following formulas were used to generate the wire distance chart:
Exception:  When using the ANN-RLY module, the installer must ensure that the maximum 
24VDC power line drop does not exceed 0.3 volts.  This results in the following wiring 
limitations:
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case Current 
Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1,852 ft.
4,688 ft.
* 6,000 ft.
*6,000 ft.
0.200
926 ft.
2,344 ft.
3,731 ft.
5,906 ft.
0.300
617 ft.
1,563 ft.
2,488 ft.
3,937 ft.
0.400
463 ft.
1,172 ft.
1,866 ft.
2,953 ft.
0.500
370 ft.
938 ft.
1,493 ft.
2,362 ft.
Table 2.1  Wiring Distances
Maximum Resistance (Ohms)
=
6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)
=
Maximum Resistance (Ohms)
*500
(6,000 feet maximum)
Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge
Ohms per 1,000 feet (Rpu)
22
16.2
18
6.4
16
4.02
14
2.54
Wire Gauge
Maximum Wire Length
18
312 feet
16
497 feet
14
787 feet
12
1,250 feet