18
deviCe SeTuP
6.7
STRIKE TIME:
5
Strike Time
This option displays if DOOR is selected as Device Type.
Enter a door access time, between 1 and 250 seconds, during which a keypad or access
control device relay is activated. Magnetic locks or electric door strikes are connected
to the relay and released for the length of the strike time. Default is 5 seconds.
Enter 0 (zero) to activate the device relay with a toggle action. This allows the user
to activate
or deactivate the device relay each time a valid user code is entered.
The device relay is activated
or deactivated until a user code is entered again.
Note: The Request to Exit door access time of a keypad or Model 733 Wiegand
Interface Module is not affected by this selection. It remains at 5 seconds.
6.8
STRIKE DELAY:
0
Strike Delay
This option displays if DOOR is selected as Device Type.
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered
or a card read occurs. When a valid code or card read or code is received, the activation
of the door strike is delayed for the number of minutes programmed. The standard door
strike message is sent to the Central Station receiver and logged in the Display Events at
the time of card read or code entry and is not delayed. During this delay, all subsequent
codes entered or cards presented to the reader for a door strike are ignored and no
record of the attempt is stored. Enter 0 (zero) to disable. Default is 0 (zero).
6.9
FIRE EXIT NO YES
Fire Exit Release
Select
YES to allow the door access relay at this address to be released whenever
Fire panic keys are pressed or a Fire or Fire Verify zone alarm is in the Status List.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire
Verify zone alarms from the Status List. Select
NO to not allow the door access relay
at this address to be released.
6.10
OUT GROUP NO YES
Output Group
Select
YES to allow the output group (relays) assigned to the user profile to turn ON
when the device relay is activated for the programmed strike time. This could be
used to operate an elevator control. Default is
NO. See the User Profiles section in
the Appendix of this document for more information about profiles.
6.11
OVERRIDE NO YES
Schedule Override
Use this option to allow door ON/OFF schedules to be overridden by the armed
condition of the system. Selecting
YES causes the on time for a door schedule to be
ignored when all areas assigned to Access Areas for this device are armed. Should
any area become disarmed after the door schedule on time, the device output turns
on. A door output which is on during a disarmed period automatically turns off when
all access areas assigned to the device become armed, even if the scheduled off
time has not been reached. This feature can be used to keep doors locked when a
factory opens late, or is forced to close early, due to a snow storm or other cause.
Select
NO to allow door schedules to operate independent of system armed status.
Note: When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS,
the door schedule for that device does not work. Either set
OVERRIDE to NO or
enter an area number in
ACCESS AREAS.
6.12
AUTO FORCE ARM
Auto Force Arm Device?
DEVICE? NO YES Select YES to have all Display Areas assigned to this keypad automatically arm and
force arm faulted zones at arming. The user is not prompted to select areas to
arm or force arm faulted zones after choosing ARM at the keypad. If Closing Code
is programmed as
YES, only the matching areas between the Display Areas and
the User Code’s authorized areas arm. Also, when
YES is selected, the user is not
prompted to select areas to disarm after entering a code at Entry Delay or after
choosing Disarm at the keypad. All matching areas assigned to the User Code and to
this keypad are automatically disarmed. When
NO is selected, the user is prompted
to select areas (ALL NO YES) and choose to force arm or bypass at arming and
disarming. Default is
NO.
6.13
DOOR REAL-TIME
Door Real-Time Status?
STATUS?
NO YES Select YES to have real-time door status messages sent to PC Log reporting and Entré
reporting for this device. Messages are sent anytime the panel turns the door relay on or
off. Default is
NO.
6.14
SEND DOOR FORCED
Send Door Forced Message?
MESSAGE? NO YES Select YES to have the panel send a real-time door status message of Forced Open (FO)
to PC Log reporting and Entré reporting when the door relay is off, but the door zone has
transitioned from its normal state. Default is
transitioned from its normal state. Default is
NO.