XR500 Series Canadian Programming Guide
18
deviCe SeTuP
6.7 
STRIKE TIME:  
5
 Strike Time
This option displays if DOOR is selected as Device Type.
Enter a door access time, between 1 and 250 seconds, during which a keypad or access 
control device relay is activated.  Magnetic locks or electric door strikes are connected 
to the relay and released for the length of the strike time.  Default is 5 seconds.
Enter 0 (zero) to activate the device relay with a toggle action. This allows the user
to activate 
or deactivate the device relay each time a valid user code is entered.  
The device relay is activated 
or deactivated until a user code is entered again.
Note: The Request to Exit door access time of a keypad or Model 733 Wiegand
Interface Module is not affected by this selection.  It remains at 5 seconds.
6.8 
STRIKE DELAY: 
0
 Strike Delay
This option displays if DOOR is selected as Device Type.
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered
or a card read occurs. When a valid code or card read or code is received, the activation
of the door strike is delayed for the number of minutes programmed.  The standard door 
strike message is sent to the Central Station receiver and logged in the Display Events at 
the time of card read or code entry and is not delayed.  During this delay, all subsequent 
codes entered or cards presented to the reader for a door strike are ignored and no 
record of the attempt is stored. Enter 0 (zero) to disable. Default is 0 (zero).
6.9 
FIRE EXIT   NO  YES
 Fire Exit Release
Select 
YES to allow the door access relay at this address to be released whenever 
Fire panic keys are pressed or a Fire or Fire Verify zone alarm is in the Status List.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire 
Verify zone alarms from the Status List. Select
NO to not allow the door access relay 
at this address to be released.
6.10 
OUT GROUP  NO  YES
 Output Group
Select 
YES to allow the output group (relays) assigned to the user profile to turn ON
when the device relay is activated for the programmed strike time.  This could be 
used to operate an elevator control.  Default is 
NO.  See the User Profiles section in 
the Appendix of this document for more information about profiles.
6.11 
OVERRIDE   NO  YES
 Schedule Override
Use this option to allow door ON/OFF schedules to be overridden by the armed
condition of the system.  Selecting 
YES causes the on time for a door schedule to be 
ignored when all areas assigned to Access Areas for this device are armed.  Should 
any area become disarmed after the door schedule on time, the device output turns 
on.  A door output which is on during a disarmed period automatically turns off when 
all access areas assigned to the device become armed, even if the scheduled off 
time has not been reached.  This feature can be used to keep doors locked when a 
factory opens late, or is forced to close early, due to a snow storm or other cause.  
Select 
NO to allow door schedules to operate independent of system armed status.
Note: When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS
the door schedule for that device does not work.  Either set 
OVERRIDE to NO or 
enter an area number in 
ACCESS AREAS
6.12 
AUTO FORCE ARM
 Auto Force Arm Device?
DEVICE?   NO  YES  Select YES to have all Display Areas assigned to this keypad automatically arm and 
force arm faulted zones at arming.  The user is not prompted to select areas to 
arm or force arm faulted zones after choosing ARM at the keypad.  If Closing Code 
is programmed as 
YES, only the matching areas between the Display Areas and 
the User Code’s authorized areas arm.  Also, when 
YES is selected, the user is not 
prompted to select areas to disarm after entering a code at Entry Delay or after 
choosing Disarm at the keypad.  All matching areas assigned to the User Code and to 
this keypad are automatically disarmed. When
NO is selected, the user is prompted 
to select areas (ALL NO YES) and choose to force arm or bypass at arming and
disarming.  Default is 
NO.
6.13 
DOOR  REAL-TIME
 Door Real-Time Status?
STATUS?  
NO  YES  Select YES to have real-time door status messages sent to PC Log reporting and Entré
reporting for this device.  Messages are sent anytime the panel turns the door relay on or 
off. Default is 
NO.
6.14 
SEND  DOOR  FORCED
 Send Door Forced Message?
MESSAGE?   NO  YES  Select YES to have the panel send a real-time door status message of Forced Open (FO)
to PC Log reporting and Entré reporting when the door relay is off, but the door zone has
transitioned from its normal state.  Default is 
NO.