zone informaTion
19.25
PRIORITY NO YES
Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
19.26
Fire Panel Slave Input
This option is available on Fire Zones (FI) only and allows a fire zone the ability to
provide slave communication operation for a separate fire alarm control panel. If
YES, this zone will transmit a restoral immediately when restored by the fire panel
being monitored. A sensor reset is not required to generate the restoral message.
If NO, this zone will operate as a standard fire type zone and a sensor reset is
If NO, this zone will operate as a standard fire type zone and a sensor reset is
required before the zone will return to normal. Default is NO.
19.27
Area Follower
Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit
or entry delay that is currently running in the area that is specified. Default is 0.
19.28
Zone Real-Time Status
Selecting YES allows Real-Time Status reports, such as Door Open or Closed with
zone number, to be sent using PC Log reporting. Selecting NO disables Real-Time
Status for this zone. Default is NO.
19.28.1
Door Number
If ZONE REAL-TIME STATUS is selected as YES, enter a door number (keypad bus
address) of 1-16. When a door number is selected, the door number is included
in the status report instead of the zone number. Enter 0 (zero) to disable this
feature and report the zone number. Default is 0 (no door).
19.29
ZONE AUDIT DAYS:
Zone Audit Days
Enter the number of days (0 to 365) allowed to elapse without the zone being tripped
before a fault message is sent. The message is sent to the receiver(s) programmed
to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
number of days programmed. Available for all zone types except fire and fire verify.
Enter 0 (zero) to disable this function. Default is 0 (zero).
19.30
Report with Account Number for Area
This option is only available for 24-hour zone types (Fire, Fire Verify, Panic,
Emergency, or Supervisory).
Enter the area number (1-32) to assign as a 24-hour zone type. This option sends
Enter the area number (1-32) to assign as a 24-hour zone type. This option sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communication section is sent. Select 0 (zero) to have the report sent with the
account number programmed in Communication. Default is 0
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS NO YES
FIRE PANEL SLAVE
INPUT: NO YES
DOOR NUMBER: 0
0
REPORT WITH ACCT
NO. FOR AREA: 0