Bosch 3.5 사용자 설명서

다운로드
페이지 498
Bosch Security Systems | 2011-02
2011-02 | Installation and User Instructions | 5 | Call Stations
en | 259
23.5 Operation
23.6 Technical data
23.6.1 Physical characteristics
23.6.2 Climate conditions
23.6.3 EMC and Safety
23.6.4 Mean time between failure 
23.6.5 System bus
23.6.6 Audio
table 23.1: Status LED indications
Yellow
(Fault)
Green
(Power)
Status
Off
Off
No power
On
On
No network or network fault
Off
On
Functioning correctly
Dimensions (H x W x D):
27 x 243 x 80 mm (without bracket)
34 x 243 x 84 mm (with bracket)
Weight:
0.7 kg
Temperature:
-5 to +55 °C (operating, guaranteed)
-15 to 55 °C (operating, sample tested)
-20 to +70 °C (non-operating)
Relative humidity:
15 to 90%, non-condensing (operating)
5 to 95%, non-condensing (non-operating)
Air pressure:
600 to 1100 hPa
Electromagnetic compatibility:
EN55103-1/FCC-47 part 15B
EN55103-2
EN50121-4
EN50130-4
Electrical safety:
IEC60065 (CB-scheme)
EN60065 
Approvals:
CE marking
EN60849, EN54-16 and ISO7240-16
IEC60945
MTBF:
50,000 hours at +55 °C
(The MTBF doubles for every 10 °C decrease in 
temperature.)
Number of connections:
2x proprietary female connectors
Position:
Front side
Preferred cable:
LBB4416/xx
Maximum cable length:
50 m
Power supply via network:
18 to 56 V(DC)
No fault reporting when >20V
Network power consumption:
4.2 W
Bandwidth:
20 Hz to 20 kHz (- 3 dB)
Data compression:
4:1 (subband coding)
Signal/Noise ratio:
> 85 dB
Crosstalk:
< -85 dB