Praesideo 3.5 | Installation and User Instructions | ISO7240-16: 2007
en | 62
7.2.2 Where a voice signal is used as part of the alert 
signal, the alert signal shall precede the first pre-recorded 
voice message for 3 s to 10 s. Successive alert signals and 
messages shall then continue until either automatically or 
manually changed or silenced. The interval between 
successive messages shall not exceed 30 s and alert 
signals shall be broadcast whenever periods of silence 
might otherwise exceed 10 s.
Praesideo offers this functionality via its call macros. The 
installer must configure the call macros accordingly.
7.2.3 Where more than one alert signal is provided, each 
signal shall be clearly distinguishable.
Praesideo offers a wide choice of independent alert and 
alarm signals.
7.3 Evacuate signal
7.3.1 The evacuate signal may be preceded by an alert 
signal (see 7.2).
The use of an alert signal, together with an evacuate signal, 
should be assessed as part of an emergency management 
plan (see ISO 7240-19). For buildings and structures 
where the plan requires the unassisted evacuation of 
occupants, the s.s.e.p. may be configured to generate a 
warning signal that does not incorporate an alert signal.
Praesideo offers the possibility to configure a call macro 
with an evacuation signal or evacuation message only.
7.3.2 The evacuate signal shall include the tone signal and 
pre-recorded voice messages, as specified in ISO 8201.
Manufacturers may implement other signal templates to 
satisfy specific mandated national requirements.
The installer must configure one of the dedicated ISO8201 
compliant evacuate signals that Praesideo offers. These 
emergency signals have the temporal pattern as described 
by ISO8201 and have a predefined name 
‘Emg x ISO8201 C’, with x being a sequential number. 
The installer must ensure that the sound pressure level of 
the evacuate signal is at least 65dBA, or 75dBA if the 
signal is intended to arouse sleeping occupants.
ISO8201 does not specify pre-recorded voice messages, 
but Praesideo offers the possibility to store and select 
custom voice messages to satisfy specific mandated 
national requirements.
7.5 Audible warning - Optional function
7.5.3 The audible warning shall be silenced automatically 
when the s.s.c.i.e. is reset from the voice alarm condition.
Praesideo silences the audible warning signal upon 
acknowledge of the voice alarm condition. Acknowledge 
and reset can be combined in a single action.
7.6 Delay before entering the voice-alarm condition - 
Optional function
d    It shall be possible to override the delay by a manual 
operation at access level 1 and/or by a signal from a 
manual call point.
Since the Praesideo system does not process the fire 
sensors, this functionality is better handled by the device 
managing the fire sensors (the CIE). The Praesideo system 
itself does not implement this requirement.
7.7 Phased evacuation - Optional function
c    When switching from phased evacuation to manual 
mode, the phased evacuation sequence shall halt.
Praesideo has multiple priority levels to override (phased 
evacuation) calls by manually activated calls.
d    When switching from manual mode to phased 
evacuation, the phased evacuation sequence shall 
resume from the point at which it was halted.
Praesideo will resume manually overruled calls without live 
speech but with emergency priority, after the overruling call 
has finished.
Clause / Requirement
Compliance
Signature
8 Fault-warning condition
8.1 Reception and processing of fault signals
8.1.2 The s.s.c.i.e. shall be capable of simultaneously 
recognizing all of the faults specified in 8.2, and in 8.3 if 
provided, unless this is prevented by 
• 
the presence of voice-alarm signals in the same 
emergency loudspeaker zone, and/or
• 
the disablement of the corresponding emergency 
loudspeaker zone or function, and/or
• 
the testing of a corresponding zone or function.
In Praesideo supervision is always active.
8.2 Indication of faults in specified functions
8.2.2 If the indication is by means of separate light-emitting 
indicators, these may be the same as those used to 
indicate disablement and/or testing of the corresponding 
emergency loudspeaker zones or functions.
Praesideo uses separate indicators for faults.
The optional disablement and test conditions are not 
supported by the Praesideo system.