TABLE 7 
LP/PROPANE GAS MANIFOLD PRESSURES - in.wg. (kPa )  
 
 ALTITUDE 
FT. 
(M)
MODEL 
0-2000 
(0-610) 
2001-3000 
(610-914) 
3001-4000 
(915-1219) 
4001-5000 
(1220-1524)
5001-6000 
(1524-1829)
6001-7000 
(1829-2134)
7001-8000 
(2134-2438) 
8001-9000 
(2439-2743)
9001-10000 
(2744-3048) 
TUA045SL 9.5 
(2.37)* 7.4 
(1.84) 6.7 
(1.67) 6.1 
(1.52)
5.5 (1.37)
4.9 (1.22)
4.4 (1.10) 3.9 
(0.97) 3.4 
(0.85)
TUA060SL 9.5 
(2.37)* 7.4 
(1.84) 6.7 
(1.67) 6.1 
(1.52)
5.5 (1.37)
4.9 (1.22)
4.4 (1.10) 3.9 
(0.97) 3.4 
(0.85)
TUA075SL 9.5 
(2.37)* 7.4 
(1.84) 6.7 
(1.67) 6.1 
(1.52)
5.5 (1.37)
4.9 (1.22)
4.4 (1.10) 3.9 
(0.97) 3.4 
(0.85)
TUA100SL 9.0 
(2.24)* 7.0 
(1.74) 6.4 
(1.59) 5.8 
(1.44)
5.2 (1.30)
4.7 (1.17)
4.2 (1.05) 3.7 
(0.92) 3.2 
(0.80)
TUA125SL 9.0 
(2.24)* 7.0 
(1.74) 6.4 
(1.59) 5.8 
(1.44)
5.2 (1.30)
4.7 (1.17)
4.2 (1.05) 3.7 
(0.92) 3.2 
(0.80)
*No adjustment required. 
 
Gas Flow 
 
Check for proper gas flow to the unit heater. 
1.  Operate unit at least 15 minutes before checking 
gas flow. Determine the time in seconds for one 
revolution of gas through the meter.  
2.  Compare the number of seconds and the gas 
meter size in table 8 to determine the gas flow rate. 
Multiply the gas flow rate by the heating value to 
determine the unit input rate. If manifold pressure is 
correct and the unit input rate is incorrect, check 
gas orifices for proper size and restriction. 
3.  Remove temporary gas meter if installed. 
 
NOTE – To obtain accurate reading, shut off all other 
gas appliances connected to meter.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
TABLE 8 
Gas Flow Rate (Ft.
3
/Hr.) 
Gas Meter Size 
Seconds for 1 
Revolution 
½ cu ft Dial 
1 cu ft Dial 
10 180 360 
12 150 300 
14 129 257 
16 113 225 
18 100 200 
20 90 180 
22 82 164 
24 75 150 
26 69 138 
28 64 129 
30 60 120 
32 56 113 
34 53 106 
36 50 100 
38 47 95 
40 45 90 
42 43 86 
44 41 82 
46 39 78 
48 38 75 
50 36 72 
52 35 69 
54 33 67 
56 32 64 
58 31 62 
60 30 60 
Natural = 1000 btu/cu ft  
LP = 2500 btu/cu ft 
Note: Table assumes standard temperature (60°F), barometric 
pressure (30 in Hg), and fuel heating values (btu/cu ft).  Fuel heating 
values may vary, contact local fuel supplier to obtain actual heating 
value of fuel being supplied.