INSTALLATION
Installation is the same for all operating positions: upflow, hori-
zontal right or left (Refer to Figure 1). Installation of the Heater
Kit should be done prior to unit installation.
1.
If Heat Kit has circuit breakers - remove circuit breaker
knockouts from front of air handler unit. For  kits  with  circuit
breakers, cut blower access panel insulation along foil
perforations behind the circuit breaker plate and remove to
open the area for the circuit breakers to protrude through
the front access panel and to provide clearance for circuit
breakers and single point wiring entry kit. Replacement
non-foil faced insulation for the exposed front panel may
then need to be added. Add rubber gasket to inside of
door.
2.
Remove air handler blower access panel.
3.
Remove duct cover from back panel of air handler control
and wiring compartment.
4.
Install electric heat accessory.
a.
Position and slide heat kit into opening in air handler.
b.
Align holes and fasten the Heat Kit to the air handler
unit with 4 screws.
5.
Connect the Heat Kit’s 6 pin socket connector to the appro-
priate 6 pin connector in the air handler. The end terminals
are “D” shaped to ensure polarization of the connector.
6.
Connect the air handler power supply to either the circuit
breaker or terminal block.
7.
Mark an X in the appropriate box on the indoor unit data
plate for the particular heater installed.
LINE POWER CONNECTIONS
Power may be brought into the unit through the outlet air end of
the unit (top left when unit is vertical) or the left side panel. To
minimize air leakage, seal the field wiring entry point.
Field wiring connects to heat kits with circuit breaker or terminal
block. A ground lug is also provided on the kits.
ELECTRIC HEATERS & OPERATING 
CONTROLS
The low voltage transformer and the fan control are standard on
all models. The air handlers are shipped pre-wired to operate
as cooling only applications.
To prevent damage, carefully pass the accessory heating ele-
ment through the rectangular opening in the discharge duct.
Element mounting plate must be secured with 4 screws.
Verify edges of foil faced insulation are not in contact with any
exposed electrical connections.
All wiring must comply with local and national electrical code
requirements. Read and heed all unit caution labels.
NOTICE
FIGURE 2: Heat Kit Connection
 
 
 
FIELD SUPPLY WIRING WILL
BE ATTACHED TO THIS SIDE
CIRCUIT BREAKERS
May be 1, 2, or 3)
UNIT WIRING ATTACHED
TO THIS SIDE
(Do not need to remove)