FAN PERFORMANCE
Table 33 – 580J*04
1 PHASE
3 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field Supplied Drive
1
Standard Static Option
Medium Static Option
900
553
0.14
681
0.22
782
0.32
870
0.42
948
0.53
975
575
0.16
700
0.25
801
0.35
888
0.46
965
0.57
1050
597
0.18
720
0.28
820
0.38
906
0.49
983
0.61
1125
620
0.21
741
0.31
839
0.42
925
0.54
1001
0.66
1200
643
0.23
762
0.34
859
0.46
944
0.58
1020
0.71
1275
667
0.27
783
0.38
879
0.50
963
0.63
1038
0.76
1350
691
0.30
805
0.42
900
0.55
983
0.68
1057
0.82
1425
715
0.34
827
0.47
920
0.60
1002
0.74
1076
0.88
1500
740
0.38
849
0.52
941
0.66
1023
0.80
1096
0.95
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field Supplied Drive
2
900
1019
0.64
1084
0.76
1146
0.89
1203
1.02
1258
1.16
975
1036
0.69
1101
0.81
1162
0.94
1219
1.08
---
---
1050
1053
0.74
1118
0.86
1179
1.00
1236
1.14
---
---
1125
1071
0.79
1135
0.92
1196
1.06
1253
1.20
---
---
1200
1089
0.84
1153
0.98
1213
1.12
---
---
---
---
1275
1107
0.90
1171
1.04
1231
1.19
---
---
---
---
1350
1126
0.96
1189
1.11
---
---
---
---
---
---
1425
1144
1.03
1208
1.18
---
---
---
---
---
---
1500
1163
1.10
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field supplied drive is required.
1. Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).
2. Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).
Table 34 – 580J*04
1 PHASE
3 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field Supplied Drive
1
Standard Static Option
Medium Static Option
900
567
0.15
688
0.22
786
0.30
871
0.37
947
0.44
975
591
0.17
710
0.26
807
0.34
891
0.42
966
0.49
1050
615
0.20
732
0.29
828
0.38
911
0.47
985
0.55
1125
641
0.23
755
0.33
849
0.42
931
0.52
1005
0.61
1200
666
0.26
778
0.37
871
0.47
952
0.57
1025
0.67
1275
693
0.29
802
0.41
893
0.53
974
0.63
1046
0.74
1350
719
0.33
826
0.46
916
0.58
995
0.70
1067
0.81
1425
746
0.38
850
0.51
939
0.64
1017
0.76
1088
0.89
1500
773
0.42
875
0.57
963
0.70
1040
0.84
1110
0.96
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field Supplied Drive
2
900
1016
0.51
1080
0.57
1139
0.64
1195
0.71
1249
0.77
975
1034
0.57
1098
0.64
1157
0.72
1213
0.79
1266
0.86
1050
1053
0.63
1116
0.71
1176
0.79
1231
0.87
1284
0.95
1125
1073
0.70
1135
0.79
1194
0.87
1250
0.96
1302
1.04
1200
1093
0.77
1155
0.87
1213
0.96
1268
1.05
1321
1.14
1275
1113
0.85
1174
0.95
1232
1.05
1287
1.15
---
---
1350
1133
0.92
1194
1.03
1252
1.14
---
---
---
---
1425
1154
1.01
1215
1.12
---
---
---
---
---
---
1500
1175
1.09
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field supplied drive is required.
1. Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).
2. Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).
580J