removal, to allow service access and to insure proper venti-
lation and condenser airflow.  The unit must not be installed
beneath any obstruction.  The unit should be installed re-
mote from all building exhausts to inhibit ingestion of exhaust
air into the unit fresh air intake.
INSULATED
PANELS
ROOF CURB INSTALLATION
ROOF CURB POST-INSTALLATION
CHECKS
After installation, check the top of the curb, duct connection
frame and duct flanges to make sure gasket has been ap-
plied properly.  Gasket should be firmly applied to the top of
the curb perimeter, duct flanges and any exposed duct con-
nection frame.  If gasket is loose, re-apply using strong
weather resistant adhesive.
P
ROTRUSION
Inspect curb to ensure that none of the utility services (elec-
tric) routed through the curb protrude above the curb.
I
F
 
PROTRUSIONS
 
EXIST
DO
 
NOT
 
ATTEMPT
 
TO
 
SET
 
UNIT
 
ON
 
CURB
I
NFORMATION
 
SHOWN
.
CAUTION
ROOF TOP DUCT CONNECTIONS
Install all duct connections on the unit before placing the unit
on rooftop.
RIGGING DETAILS
T
O
 
PREVENT
 
PROPERTY
 
DAMAGE
THE
 
UNIT
 
SHOULD
 
REMAIN
 
IN
 
AN
 
UPRIGHT
 
POSITION
 
DURING
 
ALL
 
RIGGING
 
AND
 
MOVING
 
OPERATIONS
T
O
 
FACILITATE
 
LIFTING
 
AND
 
MOVING
 
WHEN
 
A
 
CRANE
 
IS
 
USED
PLACE
 
THE
 
UNIT
 
IN
 
AN
 
ADEQUATE
 
CABLE
 
SLING
WARNING
D
O
 
NOT
 
LIFT
 
UNITS
 
TWO
 
AT
 
A
 
TIME
. P
ROVISIONS
 
FOR
 
FORKS
 
HAVE
 
BEEN
 
INCLUDED
 
IN
 
THE
 
UNIT
 
BASE
 
FRAME
. M
INIMUM
 
FORK
 
LENGTH
 
IS
 72” 
TO
 
PREVENT
 
DAMAGE
 
TO
 
THE
 
UNIT
.
CAUTION
Provisions for forks have been included in the unit base frame.
No other fork locations are approved.
T
O
 
PREVENT
 
POSSIBLE
 
EQUIPMENT
 
DAMAGE
PROPERTY
 
DAMAGE
PERSONAL
 
INJURY
 
OR
 
DEATH
THE
 
FOLLOWING
 
BULLET
 
POINTS
 
MUST
 
BE
 
OBSERVED
 
WHEN
 
INSTALLING
 
THE
 
UNIT
.
WARNING
Unit must be lifted by the four lifting holes located at
the base frame corners.
Lifting cables should be attached to the unit with
shackles.
The distance between the crane hook and the top of
the unit must not be less than 60”.
Two spreader bars must span over the unit to prevent
damage to the cabinet by the lift cables.  Spreader
bars must be of sufficient length so that cables do not
come in contact with the unit during transport.
Remove wood struts mounted beneath unit base
frame before setting unit on roof curb.  These struts
are intended to protect unit base frame from fork lift
damage.  Removal is accomplished by extracting the
sheet metal retainers and pulling the struts through
the base of the unit.  Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-
work should be attached to the curb prior to installing the
unit. Ductwork dimensions are shown in Roof Curb Installa-
tion Instructions.
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower
than supply air end.