Installation
VENT TERMINATION CLEARANCES:
A)
Minimum 4-foot clearance below or beside any door or window that opens.
B)
Minimum 1-foot clearance above any door or window that opens.
C)
Minimum 3-foot clearance form any adjacent building.
D)
Minimum 7-foot clearance from any grade when adjacent to public walkways.
E)
Minimum 2-foot clearance above any grass, plants, or other combustible materials.
F)
Minimum 3-foot clearance from an forced air intake of any appliance.
G)
Minimum 2-foot clearance below eves or overhang.
H)
Minimum 1-foot clearance horizontally from combustible wall.
Must be a minimum of 36-inches above the roof and 24-inches above the highest point or the roof within 10-feet.
FIGURE 6 
VENT TERMINATION CLEARANCES 