Rinnai Corporation EX17C / EX22C Manual 
 
  Gas 
Connection    
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
•  The gas supply line shall be gas tight, sized and so 
installed as to provide a supply of a gas sufficient to 
meet the maximum demand of the heater without 
loss of pressure. 
•  A shut off valve and appliance connector valve 
should be installed in the upstream of the gas line to 
permit servicing. 
•  Flexible pipe and any appliance connector valve 
used for gas piping shall be types approved by 
nationally recognized agencies. 
•  Any compound used on the threaded joint of the gas 
piping shall be a type which resists the action of 
liquefied petroleum gas (propane / LPG). 
•  After completion of gas pipe connections all joints 
including the heater must be checked for gas 
tightness by means of leak detector solution, soap 
and water, or an equivalent nonflammable solution, 
as applicable.  (Since some leak test solutions, 
including soap and water, may cause corrosion or 
stress cracking, the piping shall be rinsed with water 
after testing, unless it has been determined that the 
leak test solution is non-corrosive.) 
•  Check the gas supply pressure immediately 
upstream at a location provided by the gas 
company.  Supplied gas pressure must be within the 
limits shown in the Specifications section.   
•  Refer to an approved pipe sizing chart if in doubt 
about the size of the gas line. 
•  Install the provided manual gas shut-off valve so 
that it can be accessed for easy operation.  Do not 
conceal manual cut-off valve behind back spacer. 
  Clearances to Combustibles 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
When determining where to install the appliance 
the clearances to combustibles shown in the 
figure must be followed.  Also refer to the Safety 
Behaviors and Practices section.   
  Attach Back Covers (Sides Only)  
 
 
 
 
 
 
 
 
 
 
 
 
Attach back covers as shown. 
9 in (225 mm) are necessary from 
the top of the appliance to remove 
the filter for cleaning 
NOTICE
 
Engage lugs 
2 in  
(50 mm) 
2 in  
(50 mm) 
40 in  
(1 m) 
Zero - See Notice 
Zero 
Manual gas 
shut-off valve