Thermo Products OD6FX072DV5R 사용자 설명서

다운로드
페이지 76
 
 32 
 
M.  BLOWER CONTROLLER INFORMATION FOR PSC MOTOR 
 
(Note: for ECM blower controller information see: ECM Operation Manual document # Mo-440) 
 
TERMINAL DEFINITIONS & FIELD WIRING 
 
Burner Harness Connector P1 
 
Pin 1-  Limit switch connector. 
 
Pin 2-  120 VAC Line connection. 
 
Pin 3-  Burner pilot contact. 
 
Pin 4&5- 
120 VAC Neutral connections. 
 
Pin 6-  Burner pilot contact. 
 
Pin 7&8- 
From oil primary control. 
 
Pin 9-  Limit Switch Input (LSI).
 
 
 
Field Wiring to Burner 
            
 
 
 
  Harness 
Wires 
Beckett Connections 
  Riello 
Connections
 
 
 
Thermostat / Humidistat connections 
 “C” 
 Common 
ground 
 
“W” 
 
Thermostat call for heat 
 
“R” 
 
24 VAC to thermostat 
 
“G” 
 
Thermostat call for fan 
 
“Y” 
 
Thermostat call for cool 
 
“DEHUM” 
Humidistat call for dehumidification (TXV systems ONLY)
 
 
Male quick connect terminals. 
 “S1-3” 
 120 
VAC 
Hot 
 “N1-7” 
 120 
VAC 
Neutral 
 
“EAC”   
Electronic Air Cleaner (120 VAC) connection 
 “FAN” 
 Fan 
On 
Signal 
 
“X” 
 
24 VAC from transformer 
 
“C” 
 
24 VAC common from transformer 
 “CC” 
 Compressor 
Contactor 
 
“CC_COM” 
Compressor Contactor Common 
 “LOW” 
 Continuous 
Blower 
Speed 
 
“HEAT”  
Blower heat speed tap
 
 
 
“COOL”  
Blower cool speed tap   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Pilot (Tstat)         Neutral       Line 
Yellow Wires 
White 
Red 
T-T terminals 
White 
Black 
T-stat terminals 
White 
Black