Burner Specification & Data sheet — Beckett Gas Burners
3
Part No. 550-142-027/0508
Standard motor voltage is 120/60/1 for CG10, CG25 ,  and 
1. 
230/60/1 for CG50.
Direct Spark Ignition is standard on all models.
2. 
CG10 models are available only as OO (On-Off operation) or 
3. 
LFS (Low fire start, high fire run.  Single position air, adjust-
able opening gas valve).
CG25  and  CG50  are  available  as:  LHL  Low-high-low-off 
4. 
operation.  Two position air controlled by linkageless damper 
actuator, fixed damper pre-purge.
Must be wired with boiler temperature or pressure control 
switch or operation will be low-high-off.
MOD – On-off operation with proven low fire start and 
full  modulating  firing  conditions  with  combustion  air 
control.
Modulation control drives combustion air damper and 
fuel metering valve in response to boiler demand.  Fixed 
damper pre-purge for RM 7897C.
Open damper pre-purge for RM7840L.

Burner capacities listed for elevations up to 2,000 feet.  For 
5. 
higher  elevations,  consult  local Weil-McLain  distributor/
agent or sales office.
Gas ratings based on natural gas with heating value of 1,000 
6. 
btu per cubic foot and specific gravity of 0.60.
Boiler-burner  unit  to  be  adjusted  to  achieve  +0.10  inches 
7. 
W.C. pressure at flue collar, resulting in positive pressure in 
firebox as listed.
Minimum gas pressures listed are subject to variations due 
8. 
to job conditions.  Gas burners for other gas pressures are 
available.    Consult  local Weil-McLain  distributor/agent  or 
sales office.
Gas manifold pressures shown are for initial start-up.  Final 
9. 
pressure should be determined after checking actual gas flow 
and combustion readings.
Combustion Controls:
10. 
RM7897  flame  safeguard  control  uses  ultraviolet  elec-
a. 
tronic flame detector to monitor gas burner flame, and 
provides pre-purge programming.  “C” models provide 
10 second main flame establishing period.
RM7840L  flame  safeguard  control  monitors  the  gas 
b. 
burner flame, provides pre-purge and post-purge pro-
gramming, provides switching necessary to allow firing 
rate motor to be driven to both low fire start and high fire 
positions, prevents start-up if preignition interlock circuit 
or running interlock circuit does not “prove”, system will 
lock out on safety.  Ultraviolet sensitive electronic flame 
detector is standard.
Burners listed by Underwriters Laboratories, Inc., Canadian 
11. 
Gas Association, state of Connecticut, Fire Marshal state of 
Massachusetts, city of New York MEA, and others.
Special controls can be provided to meet other code require-
12. 
ments not listed.  Consult your local Weil-McLain distributor/
agent or sales office.
Notes for Table 1 and Table 2
Burner specifications and settings
  (continued)
Gas train components and flame safeguards
Table 2 
 
 
 
 
 
Standard Gas Control Components and Sizes in Inches
Boiler 
Model  
Number
Manual 
Hand Valve 
(Field Gas Train 
Connection)
Combination 
Diaphragm 
Operating Gas Valve 
And Regulator
Safety 
Gas Valve
Manual Checking 
Gas Valve
488R-488
1
1
1
1
588 & 688
1-1/4
1-1/4
1-1/4
1-1/4
788-988
1-1/2
1-1/2
1-1/2
1-1/2
1088R-1288
2
2
2
2
1388
2-1/2
2-1/2
2-1/2
2-1/2
Flame Safeguard Provided with Listed Control Systems by Code
Boiler 
Model 
Number
UL/ CSD1
FM
IRI
OO or LFS
LHL
MOD
OO or LFS
LHL
MOD
OO or LFS
LHL
MOD
488R-488
RM7897A
--
--
RM7897A
--
--
RM7897A
--
--
588-1388
--
RM7897C
RM7840L
--
RM7897C
RM7840L
--
RM7897C
RM7840L
Additional control suppliers are available