Calculation
Example: 
Pool surface area
16’ x 32’ (512 sq ft)
*Indoor design air temperature
83 ˚F
Pool water temperature
81 ˚F
Relative Humidity
50 %
*Outdoor design air temperature
15 ˚F
* Always use design temperatures for indoor and outdoor air temperatures.  Outdoor design temperatures    
are published by organizations such as ASHRAE.  Do not us day to day temperatures for this calculation.
1.
From Table 1, select the appropriate evaporation rate based on the room air temperature, 
water temperature, and relative humidity.     
Evaporation Rate  =  0.052 
2.
From Table 2, select the corresponding flowrate factor depending on the indoor air temperature, 
outdoor temperature, and room relative humidity.     
Flowrate Factor   =  21.70
3.
Multiply the values obtained from step 1 and step 2 to obtain the minimum CFM 
required per square foot of pool surface area.
Evaporation rate    
X         Flowrate       
=   CFM / square foot of water surface area
0.052              
X          21.70            
=   1.12 
4.
Multiply the value in step 3 by the area of the pool
Area of pool      X       Value for step 3      
=   CFM 
512
X               1.12
=    573 
System Installation
It is necessary to design and size the duct distribution system for both the supply and the exhaust 
air streams.
Proper duct design will 
Minimize air flow requirements 
Ensure a comfortable environment by using reheat if required
Optimize humidity control, including eliminating condensation on windows by 
blanketing the windows with airflow
Please refer to sketch 1 and 2 for typical duct layouts.
Note:
As a general rule, if the water temperature is maintained at 80˚F and the pool room air 
temperature is maintained at 82˚F, use a factor of 1 cfm/sq ft of pool surface or .5 cfm/sq ft of room 
area (whichever is greater) to determine amount of ventilation required.