For HVAC Installer Only • Installation Guide
1. Intended Application for DH90
The  DH90  is  intended  for  use  in  residential 
applications  to  reduce  the  indoor  humidity  levels 
and increase comfort. With the optional ventilation 
ducting and ventilation control hookup, the device 
also provides precise amounts of ventilation air.
2. Approvals
The DH90 is certified by ETL to meet UL 474 and 
CSA 22.2 No. 92.
3. Specifications
 
Model:   DH90 
 
Electrical:   110-120 VAC, 6.2 Amps, 
60 Hz, grounded
 
Capacity:   90 pints/day @ 80°F, 60% 
RH
 Inlet air temperature range:  55°F min., 100°F max.
 
Air Flow:   200 CFM without external 
ducting
 
Refrigerant Charge:   1 lb., 12 oz. R22
 
Duct Connections:  Round 10" inlet, 10" 
outlet, 6" ventilation 
inlet
 
Filter Size:   Pleated MERV 11:  
14" x 14" x 1"
 Unit Size (w/o Duct Collars):  34.5"L x 15.75"W 
x 20.875"H
 
Unit Weight:   92 lbs
 
Shipping Weight:   99 lbs
4. Installation
4.1 Installation Checklist
ImPORTANT: Prior to installation of the 
DH90, the following checklist should be 
reviewed. 
The DH90 can be installed in a variety of locations 
to  meet  the  owner’s  needs,  and  integrate  with 
existing  forced  air  systems  or  existing  ductwork 
if  desired.  Choose  a  location  with  consideration 
to  accessibility  for  service,  drain  availability,  and 
power outlet location. 
4.1A Power Accessibility
Unit should be located in an area where the cord’s 
length (10') should easily reach a 115 VAC electrical 
outlet with a minimum of a 15 A circuit capacity.
4.1B Accessibility
The installed DH90 should have at least 14 inches 
of  clearance  in  the  front  of  the  device  to  service 
the filter.
4.1C Support Structure and Suspension
Place the DH90 on supports to raise the base of the 
unit.  Do  not  place  the  DH90  directly  on  structural 
building  members  without  vibration  absorbers  or 
unwanted noise may result.
The  DH90  may  be  suspended  from  structural 
members by supporting the entire base of the unit 
via cross members, rigid frame, or the like. Do not 
hang the a DH90 from the cabinet. 
Remember to 
place a drain pan under the unit if it is suspended 
above  a  finished  area  or  above  an  area  where 
water leakage could cause damage.
4.1D Sizing Chart
*This sizing chart is based on extreme climates where Rh levels 
are between 70 and 90% outdoor Rh. For less extreme climates 
then larger homes can be adequetely served. Actual requirements 
may vary.
4.2 Electrical Requirements
WARNINg: Installation must be performed 
by a qualified service technician and must 
comply with local codes. Remove power to 
the device before installing or servicing the 
device. Failure to connect the device 
according to these instructions may result in 
damage to the device or the controls.
Dehumidifier Capacity Required to 
Maintain Desired Indoor Rh*
Home Size 
(square 
feet)
60% Indoor 
Rh
55% Indoor 
Rh
50% Indoor 
Rh
Pints/day
Pints/day
Pints/day
2080
49-54
55-58
71-78
2600
61-68
65-72
90-97
3120
75-82
79-86
95-110