Vermont Casting NVBR36 사용자 설명서
11
NVB Series B-Vent Gas Fireplace
7412950
FP567
Fig. 13 Venting configurations.
�����
����������������������
��������
����������������������
��������
Venting Runs
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
������������
��������������������������������
Horizontal Run (in feet)
Vertical Run (in feet)
A
A: Vertical installations up to 40 feet (12m) in
height. Up to a 6 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B: Vertical installations up to 40 feet (12m) in
height. Up to a 10 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
B
= Acceptable venting configuration
= Unacceptable venting configuration
= Unacceptable venting configuration
FP567a
Fig. 14 Venting configurations when installing 36GSKBB.
40
38
36
34
32
30
28
38
36
34
32
30
28
26
24
24
22
20
18
16
14
14
12
10
8
2
4 6
8 10 12 14 16 18 20
A
FP567a
Venting Run
Graph
8/17/99 djt
Horizontal Run (in feet)
Vertical Run (in feet)
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installation up to 40 feet (12m) in
height. Up to a 16 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 90 degree elbows
or four 45 degree elbows.
B: Vertical installation up to 40 feet (12m) in
height. Up to a 20 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 45 degree elbows.
B