Vermont Casting 2100 사용자 설명서

다운로드
페이지 44
25
WinterWarm Fireplace Insert or System
2000941
Custom-made floor protectors may be used if they offer 
the same protection as the approved floor protector 
described in the preceding paragraph, which in testing 
was found to have a standard K value of 0.84.  Custom-
built floor protectors must have a K value equal to, or 
less than, 0.84, meaning that heat will transfer at the 
same rate or more slowly than the tested standard.  
To calculate the thickness required for an alternate ma-
terial to result in a K value of 0.84, first determine the 
alternate material’s K factor.  This information should be 
available from your local building supply yard.  Then, 
calculate the following formula:
Let’s use brick as an example, since it is a commonly 
used hearth material.  Its K factor is 5.0.
That is, when using brick for the hearth extension, the 
brick must be a minimum of 2.6” (65 mm) thick.
Once you know the K factor of a given material, you 
can use this same formula to calculate its required 
thickness for approved hearth protection.
Flush with the Floor or Laid Over It?
Generally, it is easier to lay floor protectors over the fin-
ished floor in existing homes. In new construction, flush 
installations are a popular alternative.
When placed over a finished floor, the floor protector 
extends completely under the ventilated plinth.  (Fig. 
32) The cabinet is elevated by an amount equal to the 
thickness of the floor protector so that the plinth and 
cabinet are at the same level.  This is necessary for a 
proper fit between the WinterWarm front and the plinth.  
If you raise the cabinet more than 1” (25 mm), a corre-
sponding increase in the height of the framed chase is 
required to retain adequate clearance.
When the floor protector is installed flush, the Winter-
Warm cabinet rests on plywood shimming that brings it 
level with the finished floor.  (Fig. 33)
Whichever method you choose, the floor protector must 
satisfy the requirements outlined above, and the 3” x 
38” (76 x 965 mm) sheet metal spark protector strip 
(included) must be laid under the junction of the cabinet 
and the ventilated plinth. 
Important Reminders:
1.  INSTALL ONLY AS ILLUSTRATED.
2.  Elevating the cabinet requires a corresponding in-
crease in the height of the chase to retain adequate 
clearances. Refer to the chase specifications on 
Page 20 and double-check that all clearances will be 
satisfied.
3.  The air inlet through the ventilated plinth must not be 
blocked.
4.  A 3” x 38” (76 mm x 965 mm) strip of sheet metal 
(included in your Fireplace System) must be placed 
as a spark protector painted-side up underneath the 
joint between the front of the cabinet and the venti-
lated plinth.
FP1109
WinterWarm
raised hearth
4/05/01  djt
Over-laid Floor 
Protector
24ga. Galva-
nized Sheet 
Metal
Finished 
Floor
Sub-floor
Ventilated 
Plinth
Spark 
Protector 
Strip
Cabinet 
Base
Plywood Shim
FP1109
Fig. 32  The components of a raised hearth. The floor protec-
tor is placed over the finished floor and extends completely 
under the ventilated plinth.
FP1110
WinterWarm
Flush hearth
4/05/01  djt
Inlaid Floor 
Protector
24ga. Galva-
nized Sheet 
Metal
Finished 
Floor
Sub-floor
Ventilated 
Plinth
Spark 
Protector 
Strip
Cabinet 
Base
Plywood Shim
FP1110
Fig. 33  The components of a flush hearth. The floor protector 
is inlaid flush with the finished floor.
(K factor
of alternate
material)
(K factor of
Wonderboard)
(Thickness of
Wonderboard
required)
(Required thickness 
of alternate material)
X
=
(5.0)
(0.84)
X   (7/16” [11 mm]) = 2.6” (65 mm)