Preparation
VENTILATION
   WARNING: FOLLOW THE MINIMUM FRESH, OUTSIDE  
    AIR VENTILATION REQUIREMENTS. IF PROPER  
    FRESH, OUTSIDE AIR VENTILATION IS NOT  
    PROVIDED,  CARBON  MONOXIDE  POISONING  
    CAN OCCUR. PROVIDE PROPER FRESH, OUTSIDE  
    AIR VENTILATION BEFORE RUNNING HEATER.
Fresh Air Opening Requirements:
 
Heater Size 
  Square Feet Opening
 
350,000 Btu/Hr    10.5
Note: If you use more than one heater, provide extra fresh 
air. Provide a fresh air opening of at least three square feet 
for each 100,000 Btu/Hr rating.
FUELS
  WARNING: USE ONLY KEROSENE OR #1 FUEL OIL  
    TO AVOID RISK OF FIRE OR EXPLOSION. NEVER  
    USE  GASOLINE,  NAPHTHA,  PAINT  THINNERS,  
    ALCOHOL  OR  OTHER  HIGHLY  FLAMMABLE  
    FUELS.
Do not use heavy fuels such as No. 2 fuel oil or No. 2 diesel. 
Using heavy fuels will result in:
•  clogged fuel filter and nozzle
•  carbon build-up on spark plug
•  the need of non-toxic anti-icer in fuel during very cold 
weather
IMPORTANT: Use a KEROSENE ONLY storage container. 
Be sure storage container is clean. Foreign matter such as 
rust, dirt or water will cause flame-out control to shut down 
heater. Foreign matter may also require you to clean fuel 
system often.