Preparation
VENTILATION
   WARNING: PROVIDE A FRESH AIR OPENING OF   
    AT LEAST THREE SQUARE FEET (2,800 SQUARE  
    CM)  FOR  EACH  100,000  BTU  /  HR  RATING.  
    PROVIDE    EXTRA  FRESH  AIR  IF  MORE  
    SPACE HEATERS ARE BEING USED. THE MINIMUM  
    VENTILATION  REQUIREMENTS  MUST  BE  
    FOLLOWED TO AVOID RISKS ASSOCIATED WITH  
    CARBON  MONOXIDE  POISONING.  MAKE  
    CERTAIN THESE REQUIREMENTS ARE MET    
    PRIOR TO OPERATING SPACE HEATER.
Example:   A  200,000  Btu  /  Hr  (58.6kw)  space  heater 
requires one of the following:
• a two-car garage door [16 feet (4.88 meter) opening]    
raised 5 inches (12.7 cm)
• a single-car garage door [9 feet (2.74 meter) opening]  
  raised 8 inches (20.3 cm)
• two, 30 inch (76.2 cm) windows raised 15 inches 
  (38.1 cm)
FUELS
WARNING:  USE  ONLY  KEROSENE,  #1/#2  DIESEL/ 
 
FUEL OIL, JET A  OR JP8 FUELS TO AVOID RISK  
 
OF FIRE OR EXPLOSION. NEVER USE GASOLINE,  
 
OIL DRAINED FROM CRANKCASES, NAPHTHA,  
 
PAINT THINNERS, ALCOHOL OR OTHER HIGHLY  
 
FLAMMABLE FUELS.
Use only kerosene, #1/#2 diesel / fuel oil, JET A or JP-8 fuels. 
Heavier fuels such as No. 2 fuel oil or No. 2 diesel fuel may 
also be used but will result in:
• noticeable odor
• additional fuel filter maintenance
• the need for nontoxic, anti-icer additives in very cold      
  weather
Do not use fuels heavier than No. 2 grade or heavy oils such 
as oil drained from crankcases. These heavy oils will not 
ignite properly and will contaminate the space heater.
IMPORTANT: Use a KEROSENE ONLY (blue) or DIESEL 
ONLY (yellow) storage container. Be sure storage container 
is clean. Foreign matter such as rust, dirt, or water will cause 
the  ignition  control  assembly  to  shut  down  space  heater. 
Foreign matter may also require space heater’s fuel system 
to be frequently cleaned.