Siemens Building Technologies, Inc. 
 
7
 
Applications 
Basic Operation 
The Siemens BACnet Heat Pump Controller—Multi-Stage provides Direct Digital Control 
(DDC) technology for multiple compressor heat pump applications. Temperature control 
varies with the application. If present, mixed air temperature control and up to three stages of 
electric heat or staged heating and cooling can be provided.  
Control Temperature Setpoints 
The controller maintains a specified temperature setpoint based on Day/Night mode, the 
heating/cooling mode, and the setpoint dial (if used). 
Day/Night Mode 
The controller maintains the specified day setpoint temperature during daytime hours and the 
specified night setpoint at night. 
Night Mode Override Switch 
If the RTS has an override switch, it can be used to command the controller into day mode 
for an adjustable period of time. This only affects a controller in night mode. 
Control Loops 
Heating Loop 
 maintains room temperature setpoint by turning compressors and electric 
heat stages on and off.  
Cooling Loop 
– maintains room temperature setpoint by turning compressors on and off and 
using free cooling (mixed air control) when available. 
Mixed Air Control Loop 
The heat pump is controlled by three Proportional, Integral, and Derivative (PID) control 
loops; a cooling loop and a heating loop. This section describes the mixed air control loop.