Manual 2100-506D
Page
7 of 14
High Side Pressure:±5°
evacuated, and recharged to serial plate instructions.
Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V
SYSTEM REFRIGERANT PRESSURE CHART
Low Side pressure: ±2°
Table is based upon rated CFM (airflow) across the Evaporator 
Coil. If there is any doubt as to the correct operating charge
being in the system, the charge should be removed, system 
7961-679
50% RH
55% RH
60% RH
65% RH
70% RH
75% RH
80% RH
Low Side
96
97
98
100
102
104
106
High Side
248
253
258
261
265
269
273
Low Side
110
112
114
116
117
118
120
High Side
270
276
282
288
294
298
303
Low Side
115
119
123
127
132
136
140
High Side
297
306
315
324
333
342
351
Low Side
120
127
134
141
148
153
158
High Side
342
349
356
363
370
375
380
75° DB
80° DB
85° DB
Relative Humidity %
Return Air 
Temperature
Pressure
70° DB
TABLE  2
CHARGING PRESSURE LABEL