39
Thermostat Wiring
Thermostat Installation
The thermostat should be located on an interior wall in 
a larger room, away from supply duct drafts. DO NOT 
locate the thermostat in areas subject to sunlight, drafts 
or on external walls. The wire access hole behind the 
thermostat may in certain cases need to be sealed to 
prevent erroneous temperature measurement. Position 
the thermostat back plate against the wall so that it 
appears level and so the thermostat wires protrude 
through the middle of the back plate. Mark the position 
of the back plate mounting holes and drill holes with a 
3/16” (5mm) bit. Install supplied anchors and secure 
plate to the wall. Thermostat wire must be 18 AWG wire. 
Wire the appropriate thermostat as shown in Figures 
28a through 28c to the low voltage terminal strip on 
the CXM control board. Practically any heat pump 
thermostat will work with these units, provided it has the 
correct number of heating and cooling stages. 
Typical Thermostat Wiring, Single-Stage 
Units (2 Heat / 1 Cool)
Typical Thermostat Wiring, Two-Stage Units 
(3 Heat / 2 Cool)
Y
O
R
C
Y1/W2
O/W2
G
R
W1
W2
W/W1
FV4
Air Handler
TSTAT CCPRH01
or BBPRH01
CXM Board
(Compressor
Section)
O
G
R
C
Y/Y2
Y1
Y/Y2
From Compressor
Solenoid Valve
Hum
Humidifier
Sol. Vlv. 24VAC
S1
S2
Outdoor
Sensor
DHum
DH
C
Remove Jumper
for Dehum Mode
Notes:
1. Thermostat DIP switches must be configured for two-speed heat pump.
2. Compressor 2nd stage connection is not part of the terminal strip on
    the CXM board.  A wire nut connection is required between the
    compressor solenoid valve and Y/Y2 connection at the fan coil.
Y
O
R
C
Y1/W2
O/W2
G
R
W1
W2
W/W1
FV4
Air Handler
TSTAT CCPRH01
or BBPRH01
CXM Board
(Compressor
Section)
O
G
R
C
Y/Y2
Y1
Y/Y2
From Compressor
Solenoid Valve
Hum
Humidifier
Sol. Vlv. 24VAC
S1
S2
Outdoor
Sensor
DHum
DH
C
Remove Jumper
for Dehum Mode
Notes:
1. Thermostat DIP switches must be configured for two-speed heat pump.
2. Compressor 2nd stage connection is not part of the terminal strip on
    the CXM board.  A wire nut connection is required between the
    compressor solenoid valve and Y/Y2 connection at the fan coil.
Typical Thermostat Wiring, 
Infi nity / Evolution Controls
Y
O
C
R
B
Network
Interface Module
FE4 or Other
Communicating
 Indoor Unit
CXM Board
(Compressor
Section)
O
R
Y1
Y2
From Compressor
Solenoid Valve
(Notes 1,2)
A
D
Notes:
1. Compressor 2nd stage connection is not part of the terminal strip on
    the CXM board.  A wire nut connection is required between the
    compressor solenoid valve and N.I.M.
2. Y2 connection on N.I.M. is not used for single stage units.
C
C
B
User
Interface
D
A
C
B
D
A
C